| 2014-07-17 07:34:35 | ELECTRICAL PLAN REVIEW |
| | REVISION: 14061197 |
| | PERMIT: 14030368 |
| | ADD: 3673 HISTORIC LN. |
| | CONT: L& H HOMEBUILDERS |
| | TEL: (561) 436-0668 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | 2008 NEC |
| | |
| | 1ST REVIEW |
| | DATE: THURS. JULY 17/2014 |
| | ACTION: DENIED |
| | |
| | 1) THE REVISION INDICATES THERE IS NO INCREASE IN THE |
| | VALUE OF THE WORK AND LIST THE REVISION AS CHANGE TO |
| | MASTER BEDROOM SUITES. THE ELECTRICAL SHEETS CLEARLY |
| | SHOW THE OPTION FOR A ELEVATOR HAS BEEN TAKEN. PLEASE |
| | INCREASE THE VALUE OF THE SCOPE OF WORK TO INCLUDE THE |
| | ELEVATOR AS WELL AS THE MOVING OF THE POWDER ROOM ON |
| | THE 1ST FLOOR. REMOVAL OF EXISTING CONCRETE FLOOR, |
| | EXISTING INGROUND WASTE, RE-PIPING OF WASTE AND THE |
| | REPOURING OF THE 1ST FLOOR SLAB. 108.3* BUILDING PERMIT |
| | VALUATION. |
| | IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE |
| | CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE, |
| | ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS |
| | APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE |
| | PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES, |
| | VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL |
| | REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND |
| | SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE |
| | STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR |
| | FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR |
| | BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING |
| | COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE. |
| | VALUATION REFRENCES MAY INCLUDE THE LATEST PUBLISHED |
| | DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES |
| | (MARSHALL-SWIFT, MEANS, ETC) WITH REGIONAL ADJUSTMENTS |
| | FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE |
| | CONGRESS. |
| | |
| | 2) PLEASE PROVIDE THE MANUFACTER'S SPECIFICATIONS FOR |
| | THE NEWLY PROPOSED RESIDENTIAL ELEVATOR. PLEASE INCLUDE |
| | IN THIS INFORMATION HARDWARE ON OPENING PROTECTIVES |
| | SHALL BE OF AN APPROVED TYPE INSTALLED AS TESTED, |
| | EXCEPT THAT APPROVED INTERLOCKS, MECHANICAL LOCKS AND |
| | ELECTRIC CONTACTS, DOOR AND GATE ELECTRIC CONTACTS AND |
| | DOOR-OPERATING MECHANISMS SHALL BE EXEMPT FROM THE FIRE |
| | TEST REQUIREMENTS. 3002.1.2. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |