Plan Review Notes
Plan Review Notes For Permit 14061197
Permit Number 14061197
Review Stop E
Sequence Number 1
Notes
Date Text
2014-07-17 07:34:35ELECTRICAL PLAN REVIEW
 REVISION: 14061197
 PERMIT: 14030368
 ADD: 3673 HISTORIC LN.
 CONT: L& H HOMEBUILDERS
 TEL: (561) 436-0668
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
 2008 NEC
  
 1ST REVIEW
 DATE: THURS. JULY 17/2014
 ACTION: DENIED
  
 1) THE REVISION INDICATES THERE IS NO INCREASE IN THE
 VALUE OF THE WORK AND LIST THE REVISION AS CHANGE TO
 MASTER BEDROOM SUITES. THE ELECTRICAL SHEETS CLEARLY
 SHOW THE OPTION FOR A ELEVATOR HAS BEEN TAKEN. PLEASE
 INCREASE THE VALUE OF THE SCOPE OF WORK TO INCLUDE THE
 ELEVATOR AS WELL AS THE MOVING OF THE POWDER ROOM ON
 THE 1ST FLOOR. REMOVAL OF EXISTING CONCRETE FLOOR,
 EXISTING INGROUND WASTE, RE-PIPING OF WASTE AND THE
 REPOURING OF THE 1ST FLOOR SLAB. 108.3* BUILDING PERMIT
 VALUATION.
 IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE
 CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE,
 ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS
 APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE
 PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL
 REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND
 SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE
 STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR
 FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR
 BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING
 COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFRENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC) WITH REGIONAL ADJUSTMENTS
 FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE
 CONGRESS.
  
 2) PLEASE PROVIDE THE MANUFACTER'S SPECIFICATIONS FOR
 THE NEWLY PROPOSED RESIDENTIAL ELEVATOR. PLEASE INCLUDE
 IN THIS INFORMATION HARDWARE ON OPENING PROTECTIVES
 SHALL BE OF AN APPROVED TYPE INSTALLED AS TESTED,
 EXCEPT THAT APPROVED INTERLOCKS, MECHANICAL LOCKS AND
 ELECTRIC CONTACTS, DOOR AND GATE ELECTRIC CONTACTS AND
 DOOR-OPERATING MECHANISMS SHALL BE EXEMPT FROM THE FIRE
 TEST REQUIREMENTS. 3002.1.2.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  