2014-06-27 17:13:54RESIDENTIAL (R3) RE-ROOF, BUILDING REVIEW COMMENTS.
 CODE: 2010 FBC.
  
 1- ROOF TILE ADHESIVE:
  
 A)TILE BOND ROOF TILE ADHESIVE SUBMITTED DOESN'T MEET
 THE DESIGN PRESSURES REQUIRED BY SEC. R301 OF 2010 FBC.
 TILE BOND ADHESIVE MINIMUM ATTACHMENT RESISTANCE IS
 26.1 SEE PAGE 5 OF ROOF TILE NOA 11-0510.02. NEED AN
 ADHESIVE WITH A HIGHER MINIMUM ATTACHMENT RESISTANCE
 VALUE THAT MEETS THE DESIGN PRESSURES FOR THIS
 BUILDING. (NOTE: THE MINIMUM ATTACHMENT RESISTANCE IS
 DONE IN COMPLIANCE WITH RAS 127 CALCULATIONS).
  
 B) PROVIDE ROOF TILE ADHESIVE PRODUCT APPROVAL (2
 COPIES) THAT MEETS THE DESIGN PRESSURES OF THIS
 BUILDING. AS REQUIRED BY SEC. R301. NOTE: SEE ROOF TILE
 NOA FOR LISTED ADHESIVES.
 PRODUCT APPROVAL REQUIRED BY DCA RULE 9N-3.
  
 2- BORAL TILE SEAL NOA 12-0417.06 SUBMITTED WAS
 SUPERSEDED BY MIAMI-DADE. VISIT THE MIAMI-DADE WEBSITE
 AND DOWNLOAD CURRENT NOA. PROVIDE 2 NEW COPIES OF
 CURRENT NOA.
 REQUIRED BY DCA RULE 9N-3.
  