| Plan Review Notes For Permit 14061190 |
| Permit Number |
14061190 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-06-27 17:13:54 | RESIDENTIAL (R3) RE-ROOF, BUILDING REVIEW COMMENTS. | | | CODE: 2010 FBC. | | | | | | 1- ROOF TILE ADHESIVE: | | | | | | A)TILE BOND ROOF TILE ADHESIVE SUBMITTED DOESN'T MEET | | | THE DESIGN PRESSURES REQUIRED BY SEC. R301 OF 2010 FBC. | | | TILE BOND ADHESIVE MINIMUM ATTACHMENT RESISTANCE IS | | | 26.1 SEE PAGE 5 OF ROOF TILE NOA 11-0510.02. NEED AN | | | ADHESIVE WITH A HIGHER MINIMUM ATTACHMENT RESISTANCE | | | VALUE THAT MEETS THE DESIGN PRESSURES FOR THIS | | | BUILDING. (NOTE: THE MINIMUM ATTACHMENT RESISTANCE IS | | | DONE IN COMPLIANCE WITH RAS 127 CALCULATIONS). | | | | | | B) PROVIDE ROOF TILE ADHESIVE PRODUCT APPROVAL (2 | | | COPIES) THAT MEETS THE DESIGN PRESSURES OF THIS | | | BUILDING. AS REQUIRED BY SEC. R301. NOTE: SEE ROOF TILE | | | NOA FOR LISTED ADHESIVES. | | | PRODUCT APPROVAL REQUIRED BY DCA RULE 9N-3. | | | | | | 2- BORAL TILE SEAL NOA 12-0417.06 SUBMITTED WAS | | | SUPERSEDED BY MIAMI-DADE. VISIT THE MIAMI-DADE WEBSITE | | | AND DOWNLOAD CURRENT NOA. PROVIDE 2 NEW COPIES OF | | | CURRENT NOA. | | | REQUIRED BY DCA RULE 9N-3. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICE DEPARTMENT | | | (561)805-6712 | | | |
|