| 2014-08-22 08:16:25 | PLUMBING PLAN REVIEW |
| | PERMIT: 14061187 |
| | ADD: 900 FLORIDA AVE |
| | CONT:COASTAL CONSTRUCTION |
| | TEL: (561)630-3770 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2ND REVIEW |
| | DATE: FRI. AUG. 22/2014 |
| | ACTION: PROVISO |
| | |
| | BUILDING APPROVED WITH EXCEPTION! |
| | THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO |
| | CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO |
| | INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE |
| | ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE |
| | ADDITIONAL REVIEWS WITH ASSOCIATED FEES. |
| | |
| | NOTE:!!!!!!!! CHAPTER 553.80(2)(B) FLORIDA STATUTES |
| | STATES THAT A LOCAL GOVERNMENT SHALL IMPOSE A FEE OF |
| | FOUR TIMES THE FEE FOR PLAN REVIEW, IF PLANS ARE |
| | REJECTED OR MORE TIMES FOR REPEATED FAILURE TO CORRECT |
| | A CODE VIOLATION. |
| | |
| | 1) SHEET 0200 GP-1 THIS SHEET NOR ANY SUBMITTED |
| | PLUMBING SHEET SHOWS HOW THE STORM DRAINAGE PLANS WAS |
| | DERIVED. PLEASE PROVIDE CALCULATIONS FOR THE NOT 2ND |
| | STORY SLAB BUT THE ROOF AREA OF THE CANOPY, THE AREA OF |
| | THE CANOPY IS A LARGER SQ. FT .SURFACE AREA. PLEASE |
| | DESIGN TO THE 2010 FBC-PLUMBING 106.1 GENERAL. |
| | THE SIZE OF THE VERTICAL CONDUCTORS AND LEADERS, |
| | BUILDING STORM DRAINS, BUILDING STORM SEWERS, AND ANY |
| | HORIZONTAL BRANCHES OF SUCH DRAINS OR SEWERS SHALL BE |
| | BASED ON THE 100-YEAR HOURLY RAINFALL RATE INDICATED IN |
| | FIGURE 1106.1 OR ON OTHER RAINFALL RATES DETERMINED |
| | FROM APPROVED LOCAL WEATHER DATA. PROVIDE THE SQUARE |
| | FOOT AREA OF THE ROOFING MEMBRANE AND HOW THE DRAINAGE |
| | IS SIZED FOR THIS CANOPY AND HOW THE RAIN WATER WILL |
| | FLOW TO THE DECK DRAINS SINCE THE PLANS DO NOT INDICATE |
| | ROOF DRAINS IN THE ROOF TOP CANOPY, NOR REIN LITTERS OR |
| | CONDUCTORS TO THE ROOF DRAINS IN THE 2ND FLOOR DECK. |
| | |
| | 2) PLEASE SHOW COMPLIANCE WITH FBC-P TABLE 403.1 FOR S2 |
| | OCCUPANCY AND IF THE RESTROOMS WITHIN THE HOTEL ARE |
| | LOCATED OVER 500 FT AWAY, SEE FBC-P 403.3.2. |
| | |
| | 3) DO NOT INSTALL ANY STORM WATER BUILDING DRAIN PIPING |
| | (UNDER THE FOOTPRINT OF THE BUILDING) IDENTIFYING THE |
| | TYPE OF MATERIALS TO BE USED IN THIS INSTALLATION UNTIL |
| | A REVISION HAS BEEN SUBMITTED AND APPROVED THROUGH THE |
| | BUILDING DEPARTMENT. |
| | |
| | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |