Plan Review Notes
Plan Review Notes For Permit 14061187
Permit Number 14061187
Review Stop P
Sequence Number 2
Notes
Date Text
2014-08-22 08:16:25PLUMBING PLAN REVIEW
 PERMIT: 14061187
 ADD: 900 FLORIDA AVE
 CONT:COASTAL CONSTRUCTION
 TEL: (561)630-3770
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2ND REVIEW
 DATE: FRI. AUG. 22/2014
 ACTION: PROVISO
  
 BUILDING APPROVED WITH EXCEPTION!
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE
 ADDITIONAL REVIEWS WITH ASSOCIATED FEES.
  
 NOTE:!!!!!!!! CHAPTER 553.80(2)(B) FLORIDA STATUTES
 STATES THAT A LOCAL GOVERNMENT SHALL IMPOSE A FEE OF
 FOUR TIMES THE FEE FOR PLAN REVIEW, IF PLANS ARE
 REJECTED OR MORE TIMES FOR REPEATED FAILURE TO CORRECT
 A CODE VIOLATION.
  
 1) SHEET 0200 GP-1 THIS SHEET NOR ANY SUBMITTED
 PLUMBING SHEET SHOWS HOW THE STORM DRAINAGE PLANS WAS
 DERIVED. PLEASE PROVIDE CALCULATIONS FOR THE NOT 2ND
 STORY SLAB BUT THE ROOF AREA OF THE CANOPY, THE AREA OF
 THE CANOPY IS A LARGER SQ. FT .SURFACE AREA. PLEASE
 DESIGN TO THE 2010 FBC-PLUMBING 106.1 GENERAL.
 THE SIZE OF THE VERTICAL CONDUCTORS AND LEADERS,
 BUILDING STORM DRAINS, BUILDING STORM SEWERS, AND ANY
 HORIZONTAL BRANCHES OF SUCH DRAINS OR SEWERS SHALL BE
 BASED ON THE 100-YEAR HOURLY RAINFALL RATE INDICATED IN
 FIGURE 1106.1 OR ON OTHER RAINFALL RATES DETERMINED
 FROM APPROVED LOCAL WEATHER DATA. PROVIDE THE SQUARE
 FOOT AREA OF THE ROOFING MEMBRANE AND HOW THE DRAINAGE
 IS SIZED FOR THIS CANOPY AND HOW THE RAIN WATER WILL
 FLOW TO THE DECK DRAINS SINCE THE PLANS DO NOT INDICATE
 ROOF DRAINS IN THE ROOF TOP CANOPY, NOR REIN LITTERS OR
 CONDUCTORS TO THE ROOF DRAINS IN THE 2ND FLOOR DECK.
  
 2) PLEASE SHOW COMPLIANCE WITH FBC-P TABLE 403.1 FOR S2
 OCCUPANCY AND IF THE RESTROOMS WITHIN THE HOTEL ARE
 LOCATED OVER 500 FT AWAY, SEE FBC-P 403.3.2.
  
 3) DO NOT INSTALL ANY STORM WATER BUILDING DRAIN PIPING
 (UNDER THE FOOTPRINT OF THE BUILDING) IDENTIFYING THE
 TYPE OF MATERIALS TO BE USED IN THIS INSTALLATION UNTIL
 A REVISION HAS BEEN SUBMITTED AND APPROVED THROUGH THE
 BUILDING DEPARTMENT.
  
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  