| 2014-08-28 17:42:06 | 900 FLORIDA AVENUE |
| | PERMIT #14061187 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | ***OWNER IS PROCEEDING CONSTRUCTION AT RISK - THE |
| | FOLLOWING FIRE CODE DEFICIENCIES WILL NEED TO BE |
| | ADDRESSED PRIOR TO ISSUANCE OF A CERTIFICATE OF |
| | OCCUPANCY (CO)*** |
| | |
| | |
| | REPEAT COMMENT - SHEET GA2.00 SECTION HEADING "FIRE |
| | PROTECTION" INDICATES A COMPLETE AUTOMATIC SPRINKLER |
| | SYSTEM IS PROVIDED FOR THE ROOF LEVEL CANOPY |
| | PROTECTION; HOWEVER, SHEET GFP-2 DOES NOT INDICATE ANY |
| | AUTOMATIC SPRINKLER SYSTEM PROTECTION. |
| | |
| | SAFRSHADE CANOPY: SUBMIT PRODUCT INFORMATION AND |
| | INDICATE COMPLIANCE WITH NFPA 701. |
| | |
| | SAFRSHADE CANOPY: PER NFPA 101 THE LIFE SAFETY CODE, |
| | SECTION 11.9.1.2 "USE OF MEMBRANE ROOFS. MEMBRANE ROOFS |
| | SHALL BE USED IN ACCORDANCE WITH THE FOLLOWING: |
| | (1) MEMBRANE MATERIALS SHALL NOT BE USED WHERE FIRE |
| | RESISTANCE RATINGS ARE REQUIRED FOR WALLS OR ROOFS. |
| | (2) WHERE EVERY PART OF THE ROOF, INCLUDING THE ROOF |
| | MEMBRANE, IS NOT LESS THAN 20 FEET ABOVE ANY FLOOR, |
| | BALCONY, OR GALLERY, A NONCOMBUSTIBLE OR |
| | LIMITED-COMBUSTIBLE MEMBRANE SHALL BE PERMITTED TO BE |
| | USED AS THE ROOF IN ANY CONSTRUCTION TYPE. |
| | (3) WITH APPROVAL OF THE AUTHORITY HAVING JURISDICTION, |
| | MEMBRANE MATERIALS SHALL BE PERMITTED TO BE USED WHERE |
| | EVERY PART OF THE ROOF MEMBRANE IS SUFFICIENTLY ABOVE |
| | EVERY SIGNIFICANT FIRE POTENTIAL, SUCH THAT THE IMPOSED |
| | TEMPERATURE CANNOT EXCEED THE CAPABILITY OF THE |
| | MEMBRANE, INCLUDING SEAMS, TO MAINTAIN ITS STRUCTURAL |
| | INTEGRITY. |
| | |
| | WESLEY JOLIN |
| | ASSISTANT FIRE MARSHAL |
| | WEST PALM BEACH FIRE RESCUE |
| | [email protected] |
| | (561) 805-6730 |