Plan Review Notes
Plan Review Notes For Permit 14061187
Permit Number 14061187
Review Stop E
Sequence Number 2
Notes
Date Text
2014-08-21 07:15:11DATE: 8/21/2014
 PROJECT: 900 FLORIDA AVENUE PARKING GARAGE
 PERMIT: 14061187
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 2ND ELECTRICAL PLAN REVIEW
 ACTION: PROVISO
  
 1) SHEET T2.01,T9.11
 A. THE INTERIOR OF AN UNDERGROUND RACEWAY SHALL BE
 CONSIDERED A WET LOCATION. ALL CONDUCTORS WITHIN THE
 RACEWAY SHALL BE LISTED ACCORDINGLY.
 B. SUITABILITY FOR INSTALLATION AND USE SHALL BE IN
 CONFORMITY WITH THE PROVISIONS OF THIS CODE. NEC
 110.3(A)(1 THRU 8)
  
 2) GENERAL NOTE:
 A SEPARATE PERMIT APPLICATIONS ACCOMPANIED BY
 MANUFACTURERS EQUIPMENT SUBMITTALS, AND SHOP DRAWINGS
 ARE REQUIRED FOR GENERATOR, FIRE ALARM, SECURITY, CCTV,
 DATA/COM, NETWORK, STRUCTURED CABLING, AUDIO/VIDEO, AND
 SIGNAGE.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved