2014-08-22 09:09:03BUILDING PLAN REVIEW
 PERMIT: 14061187
 ADD: 900 FLORIDA AVE
 CONT: COASTAL CONSTRUCTION
 TEL: (561)630-3770
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
 2ND REVIEW
 DATE: FRI. AUGUST 22/ 2014
 ACTION: BUILDING PROVISO
 BUILDING APPROVED WITH EXCEPTION!
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE
 ADDITIONAL REVIEWS WITH ASSOCIATED FEES.
 1 THE OWNERS OF THE PROJECT ARE GOING TO THE STATE FOR
 A WAIVER TO THE VERTICAL ACCESSIBILITY REQUIREMENTS.
 NOTE 201.1.1 VERTICAL ACCESSIBILITY. SECTIONS
 553.501-553.513, F.S., AND THE ADA STANDARDS FOR
 ACCESSIBLE DESIGN DO NOT RELIEVE THE OWNER OF ANY
 BUILDING, STRUCTURE OR FACILITY GOVERNED BY THOSE
 SECTIONS FROM THE DUTY TO PROVIDE VERTICAL
 ACCESSIBILITY TO ALL LEVELS ABOVE AND BELOW THE
 OCCUPIABLE GRADE LEVEL REGARDLESS OF WHETHER THE
 STANDARDS REQUIRE AN ELEVATOR TO BE INSTALLED IN SUCH
 BUILDING, STRUCTURE OR FACILITY. FL S 553.509 VERTICAL
 ACCESSIBILITY. (1) THIS PART AND THE AMERICANS WITH
 DISABILITIES ACT STANDARDS FOR ACCESSIBLE DESIGN DO NOT
 RELIEVE THE OWNER OF ANY BUILDING, STRUCTURE, OR
 FACILITY GOVERNED BY THIS PART FROM THE DUTY TO PROVIDE
 VERTICAL ACCESSIBILITY TO ALL LEVELS ABOVE AND BELOW
 THE OCCUPIABLE GRADE LEVEL, REGARDLESS OF WHETHER THE
 STANDARDS REQUIRE AN ELEVATOR TO BE INSTALLED IN SUCH
 BUILDING, STRUCTURE, OR FACILITY.
 IF THE WAIVER IS DENIED THEN THE OWNERS WILL BE
 REQUIRED TO SUPPLY VERTICAL ACCESSIBILITY TO THE 2ND
 FLOOR LEVEL.
  
 2) REVISION REQUIRED, SPOKE WITH THE DESIGNER OF
 RECORD. SHEET GA2.00 CONSTRUCTION TYPE LISTED AS IB
 CONFLICT WITH 2010 FBC-B 3102.6 MIXED CONSTRUCTION.
 2010 FBC-B 406.3.6 OPEN PARKING GARAGES LESS THAN 75
 FT. IN HEIGHT UNLIMITED AREA WHEN THE TOTAL AREA OF
 OPENINGS ALONG THE SIDE SHALL NOT BE LESS THAN 50
 PERCENT OF THE INTERIOR AREA OF THE SIDE AT EACH TIER
 AND SUCH OPENINGS SHALL BE EQUALLY DISTRIBUTED ALONG
 THE LENGTH OF THE TIER. ALL PORTIONS OF TIERS SHALL BE
 WITHIN 200 FEET (60 960 MM) HORIZONTALLY FROM SUCH
 OPENINGS OR OTHER NATURAL VENTILATION OPENINGS AS
 DEFINED IN SECTION 406.3.3.1. THESE OPENINGS SHALL BE
 PERMITTED TO BE PROVIDED IN COURTS WITH A MINIMUM
 DIMENSION OF 20 FEET (6096 MM) FOR THE FULL WIDTH OF
 THE OPENINGS.
 THIS WILL ALLOW FOR THE MEMBRANE CANOPY ON A IIB
 BUILDING AND CODE COMPLIANCE.
  
 3) DEFERRED SUBMITTAL 107.3.4.2. SHEET GA8.00 NOTE # 27
 FIXED CANVAS CANOPY, THERE IS NO WIND DESIGN CRITERIA
 FOR THIS PRODUCT NOR IS THERE . 2010 FBC-B 3102.7
 ENGINEERING DESIGN. THE STRUCTURE SHALL BE DESIGNED AND
 CONSTRUCTED TO SUSTAIN DEAD LOADS; LOADS DUE TO TENSION
 OR INFLATION; AND LIVE LOADS INCLUDING WIND LOADS AND
 FLOOD IN ACCORDANCE WITH CHAPTER 16.
  
 4) DEFERRED SUBMITTAL 107.3.4.2. PLEASE PROVIDE
 COMPLIANCE WITH 2010 FBC-B 1607.7.3 VEHICLE BARRIER
 SYSTEMS FOR THE 2ND FLOOR PERIMETER BARRIER AND RAMP.
 VEHICLE BARRIER SYSTEMS FOR PASSENGER VEHICLES SHALL BE
 DESIGNED TO RESIST A SINGLE LOAD OF 6,000 POUNDS (26.70
 KN) APPLIED HORIZONTALLY IN ANY DIRECTION TO THE
 BARRIER SYSTEM AND SHALL HAVE ANCHORAGE OR ATTACHMENT
 CAPABLE OF TRANSMITTING THIS LOAD TO THE STRUCTURE.
  
 5A) DEFERRED SUBMITTAL 107.3.4.2.. SHEET GA8.00 NOTE #
 31 CABLE GUARDRAIL, GUARDRAILS ALSO INDICATE A FABRIC
 SCREEN TO BE ATTACHED TO THE GUARDRAIL SYSTEM, PLEASE
 PROVIDE INFORMATION ON FABRIC, COMPLIANCE WITH FIRE
 PROPAGATION PERFORMANCE CRITERIA OF NFPA 701.
  
 5B) DEFERRED SUBMITTAL 107.3.4.2. SHEET GA8.00 NOTE #
 31 CABLE GUARDRAIL, GUARDRAILS ALSO INDICATE A FABRIC
 SCREEN TO BE ATTACHED TO THE GUARDRAIL SYSTEM, SHOW
 COMPLIANCE WITH : 3102.7 ENGINEERING DESIGN. THE
 STRUCTURE SHALL BE DESIGNED AND CONSTRUCTED TO SUSTAIN
 DEAD LOADS; LOADS DUE TO TENSION OR INFLATION; AND LIVE
 LOADS INCLUDING WIND LOADS IN ACCORDANCE WITH CHAPTER
 16.
  
 7) ROOF CANOPY IS TO BE UNDER A SEPARATE PERMIT. NOTE
 CONTRACTOR CONTINUES AT OWN RISK.
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676