| 2014-07-09 15:34:34 | PLUMBING PLAN REVIEW |
| | PERMIT: 14061187 |
| | ADD: 900 FLORIDA AVE |
| | CONT: |
| | TEL: (561 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 1ST REVIEW |
| | DATE: WED. JULY 09/2014 |
| | ACTION: DENIED |
| | |
| | 1) SHEET 0200 GP-1 THIS SHEET NOR ANY SUBMITTED |
| | PLUMBING SHEET SHOWS HOW THE STORM DRAINAGE PLANS WAS |
| | DERIVED. PLEASE PROVIDE CALCULATIONS FOR THE NOT 2ND |
| | STORY SLAB BUT THE ROOF AREA OF THE CANOPY, PLEASE |
| | DESIGN TO THE 2010 FBC-PLUMBING 106.1 GENERAL. |
| | THE SIZE OF THE VERTICAL CONDUCTORS AND LEADERS, |
| | BUILDING STORM DRAINS, BUILDING STORM SEWERS, AND ANY |
| | HORIZONTAL BRANCHES OF SUCH DRAINS OR SEWERS SHALL BE |
| | BASED ON THE 100-YEAR HOURLY RAINFALL RATE INDICATED IN |
| | FIGURE 1106.1 OR ON OTHER RAINFALL RATES DETERMINED |
| | FROM APPROVED LOCAL WEATHER DATA. PROVIDE THE SQUARE |
| | FOOT AREA OF THE ROOFING MEMBRANE AND HOW THE DRAINAGE |
| | IS SIZED FOR THIS CANOPY AND LOCATION OF ROOF DRAINS IN |
| | THE DECK. |
| | |
| | 2) PLEASE SHOW COMPLIANCE WITH FBC-P TABLE 403.1 FOR S2 |
| | OCCUPANCY AND IF THE RESTROOMS WITHIN THE HOTEL ARE |
| | LOCATED OVER 500 FT AWAY, SEE FBC-P 403.3.2. |
| | |
| | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |