2014-08-16 16:28:00DATE: 8/16/2014
 PROJECT: 900 FLORIDA AVENUE PARKING GARAGE
 PERMIT: 14061187
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 1ST ELECTRICAL PLAN REVIEW
 ACTION: PROVISO
  
 SHEET GE.0
 1) PROVIDE SAFETY LABELING FOR ARC FLASH PROTECTION FOR
 THE PANEL BOARDS AND MAIN DISCONNECTING MEANS. NEC
 110.16, 110.22
 2) SHEET GE.1
 PROVIDE PROTECTIVE BOLLARDS FOR ELECTRICAL SWITCH GEAR
 AND FACP BUT MAINTAIN CLEARANCES PER NEC 110.26 AND
 110.27
 ALL LIGHTING TO BE IDENTIFIED ?SUITABLE FOR DAMP
 LOCATION?. NEC 110.3, AND 410.10
  
 3) SHEET T2.01,T9.11
 A. THE INTERIOR OF AN UNDERGROUND RACEWAY SHALL BE
 CONSIDERED A WET LOCATION. ALL CONDUCTORS WITHIN THE
 RACEWAY SHALL BE LISTED ACCORDINGLY.
 B. SUITABILITY FOR INSTALLATION AND USE SHALL BE IN
 CONFORMITY WITH THE PROVISIONS OF THIS CODE. NEC
 110.3(A)(1 THRU 8)
  
 4) GENERAL NOTE:
 A SEPARATE PERMIT APPLICATIONS ACCOMPANIED BY
 MANUFACTURERS EQUIPMENT SUBMITTALS, AND SHOP DRAWINGS
 ARE REQUIRED FOR GENERATOR, FIRE ALARM, SECURITY, CCTV,
 DATA/COM, NETWORK, STRUCTURED CABLING, AUDIO/VIDEO, AND
 SIGNAGE.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  