Plan Review Notes
Plan Review Notes For Permit 14061187
Permit Number 14061187
Review Stop B
Sequence Number 1
Notes
Date Text
2014-07-09 15:17:01BUILDING PLAN REVIEW
 PERMIT: 14061187
 ADD: 900 FLORIDA AVE
 CONT: COASTAL CONSTRUCTION
 TEL: (561)630-3770
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. JULY 09/2014
 ACTION: DENIED
  
 1) 0110 GA2.00 NOTES FOR FIRE PROTECTION ARE CONFUSING,
 IS OR IS NOT THIS STRUCTURE FIRE SPRINKLERED?
 TABLE 1016.1 300' FOR OPEN PARKING GARAGES
 NON-SPRINKLERED
 1018.4 DEAD END EXC # 2 50 FT W/ FIRE SPRINKLERS
 1014.3 COMMON PATH OF TRAVEL 50'-0" EXC # 8 PARKING
 GAGARES
 GFP1, GFP2 & GFP3 ONLY SHOW A DRY STAND PIPE SYSTEM.
 GFA-2 INDICATES THE INSTALATION OF A TAMPER & FLOW
 SWITCH.
  
 2) 0150 GS0.00 INDICATES A GEOTECHNICAL SOILS
 ENGINEERING REPORT WAS COMPLETED ON 6/05/13. 2010 FBC-B
 1803.3 BASIS OF INVESTIGATION. SOIL CLASSIFICATION
 SHALL BE BASED ON OBSERVATION AND ANY NECESSARY TESTS
 OF THE MATERIALS DISCLOSED BY BORINGS, TEST PITS OR
 OTHER SUBSURFACE EXPLORATION MADE IN APPROPRIATE
 LOCATIONS. ADDITIONAL STUDIES SHALL BE MADE AS
 NECESSARY TO EVALUATE SLOPE STABILITY, SOIL STRENGTH,
 POSITION AND ADEQUACY OF LOAD-BEARING SOILS, THE EFFECT
 OF MOISTURE VARIATION ON SOIL-BEARING CAPACITY,
 COMPRESSIBILITY,
 LIQUEFACTION AND EXPANSIVENESS.
  
 3) THE PLANS SHOW STAIRS TO THE 2ND LEVEL BUT NO
 ELEVATOR. PLEASE SHOW COMPLIANCE WITH VERTICAL
 ACCESSIBILITY. 201.1.1 VERTICAL ACCESSIBILITY. SECTIONS
 553.501-553.513, F.S., AND THE ADA STANDARDS FOR
 ACCESSIBLE DESIGN DO NOT RELIEVE THE OWNER OF ANY
 BUILDING, STRUCTURE OR FACILITY GOVERNED BY THOSE
 SECTIONS FROM THE DUTY TO PROVIDE VERTICAL
 ACCESSIBILITY TO ALL LEVELS ABOVE AND BELOW THE
 OCCUPIABLE GRADE LEVEL REGARDLESS OF WHETHER THE
 STANDARDS REQUIRE AN ELEVATOR TO BE INSTALLED IN SUCH
 BUILDING, STRUCTURE OR FACILITY.
 553.509?VERTICAL ACCESSIBILITY.?
 (1)?THIS PART AND THE AMERICANS WITH DISABILITIES ACT
 STANDARDS FOR ACCESSIBLE DESIGN DO NOT RELIEVE THE
 OWNER OF ANY BUILDING, STRUCTURE, OR FACILITY GOVERNED
 BY THIS PART FROM THE DUTY TO PROVIDE VERTICAL
 ACCESSIBILITY TO ALL LEVELS ABOVE AND BELOW THE
 OCCUPIABLE GRADE LEVEL, REGARDLESS OF WHETHER THE
 STANDARDS REQUIRE AN ELEVATOR TO BE INSTALLED IN SUCH
 BUILDING, STRUCTURE, OR FACILITY, EXCEPT FOR:
 (A)?ELEVATOR PITS, ELEVATOR PENTHOUSES, MECHANICAL
 ROOMS, PIPING OR EQUIPMENT CATWALKS, AND AUTOMOBILE
 LUBRICATION AND MAINTENANCE PITS AND PLATFORMS.
 (B)?UNOCCUPIABLE SPACES, SUCH AS ROOMS, ENCLOSED
 SPACES, AND STORAGE SPACES THAT ARE NOT DESIGNED FOR
 HUMAN OCCUPANCY, FOR PUBLIC ACCOMMODATIONS, OR FOR WORK
 AREAS.
 (C)?OCCUPIABLE SPACES AND ROOMS THAT ARE NOT OPEN TO
 THE PUBLIC AND THAT HOUSE NO MORE THAN FIVE PERSONS,
 INCLUDING, BUT NOT LIMITED TO, EQUIPMENT CONTROL ROOMS
 AND PROJECTION BOOTHS.
 (D)?THEATERS, CONCERT HALLS, AND STADIUMS, OR OTHER
 LARGE ASSEMBLY AREAS THAT HAVE STADIUM-STYLE SEATING OR
 TIERED SEATING IF SS. 221 AND 802 OF THE STANDARDS ARE
 MET.
 (E)?ALL PLAY AND RECREATION AREAS IF THE REQUIREMENTS
 OF CHAPTER 10 OF THE STANDARDS ARE MET.
 (F)?ALL EMPLOYEE AREAS AS EXEMPTED IN S. 203.9 OF THE
 STANDARDS.
 (G)?FACILITIES, SITES, AND SPACES EXEMPTED BY S. 203 OF
 THE STANDARDS.
 (2)?HOWEVER, BUILDINGS, STRUCTURES, AND FACILITIES
 MUST, AS A MINIMUM, COMPLY WITH THE AMERICANS WITH
 DISABILITIES ACT STANDARDS FOR ACCESSIBLE DESIGN.
  
 4A) SHEET GA8.00 NOTE # 27 FIXED CANVAS CANOPY, THERE
 IS NO WIND DESIGN CRITERIA FOR THIS PRODUCT NOR IS
 THERE . 2010 FBC-B 3102.7 ENGINEERING DESIGN. THE
 STRUCTURE SHALL BE DESIGNED AND CONSTRUCTED TO SUSTAIN
 DEAD LOADS; LOADS DUE TO TENSION OR INFLATION; AND LIVE
 LOADS INCLUDING WIND LOADS AND FLOOD IN ACCORDANCE WITH
 CHAPTER 16.
  
 4B) THE FIXED CANVAS CANOPY IS ONTOP OF A BUILDING TYPE
 I-B PLEASE INDICATE HOW COMPLIANCE WITH THE FOLLOWING:
 2010 FBC-B 3102.6 MIXED CONSTRUCTION.
 MEMBRANE STRUCTURES SHALL BE PERMITTED TO BE UTILIZED
 AS SPECIFIED IN THIS SECTION AS A PORTION OF BUILDINGS
 OF OTHER TYPES OF CONSTRUCTION. HEIGHT AND AREA LIMITS
 SHALL BE AS SPECIFIED FOR THE TYPE OF CONSTRUCTION AND
 OCCUPANCY OF THE BUILDING.
  
 3102.6.1 NONCOMBUSTIBLE MEMBRANE.
 A NONCOMBUSTIBLE MEMBRANE SHALL BE PERMITTED FOR USE AS
 THE ROOF OR AS A SKYLIGHT OF ANY BUILDING OR ATRIUM OF
 A BUILDING OF ANY TYPE OF CONSTRUCTION PROVIDED IT IS
 AT LEAST 20 FEET (6096 MM) ABOVE ANY FLOOR, BALCONY OR
 GALLERY.
  
 3102.6.1.1 MEMBRANE.
 A MEMBRANE MEETING THE FIRE PROPAGATION PERFORMANCE
 CRITERIA OF NFPA 701 SHALL BE PERMITTED TO BE USED AS
 THE ROOF OR AS A SKYLIGHT ON BUILDINGS OF TYPES IIB,
 III, IV AND V CONSTRUCTION, PROVIDED IT IS AT LEAST 20
 FEET (6096 MM) ABOVE ANY FLOOR, BALCONY OR GALLERY.
  
 4C) SHEET GA8.00 NOTE # 31 CABLE GUARDRAIL, GUARDRAILS
 TO REJECT A 4 INCH SPHERE. PLEASE PROVIDE AT WHAT
 CENTERS THE CABLE WILL NEED TO BE, CENTER TO CENTER ON
 POST AND AT WHAT TENSION IT WILL TAKE TO KEEP THE
 SPHERE FROM GOING THROUGH THE SPACING OF THE CABLES.
 2010 FBC-B 1013.3.
  
 4D)(1) SHEET GA8.00 NOTE # 31 CABLE GUARDRAIL,
 GUARDRAILS ALSO INDICATE A FABRIC SCREEN TO BE ATTACHED
 TO THE GUARDRAIL SYSTEM, PLEASE PROVIDE INFORMATION ON
 FABRIC, COMPLIANCE WITH FIRE PROPAGATION PERFORMANCE
 CRITERIA OF NFPA 701.
  
 4D)(2) SHEET GA8.00 NOTE # 31 CABLE GUARDRAIL,
 GUARDRAILS ALSO INDICATE A FABRIC SCREEN TO BE ATTACHED
 TO THE GUARDRAIL SYSTEM,
 SHOW COMPLIANCE WITH : 3102.7 ENGINEERING DESIGN.
 THE STRUCTURE SHALL BE DESIGNED AND CONSTRUCTED TO
 SUSTAIN DEAD LOADS; LOADS DUE TO TENSION OR INFLATION;
 AND LIVE LOADS INCLUDING WIND LOADS IN ACCORDANCE WITH
 CHAPTER 16.
  
 4E) PLEASE PROVIDE COMPLIANCE WITH 2010 FBC-B 1607.7.3
 VEHICLE BARRIER SYSTEMS FOR THE 2ND FLOOR AND RAMP.
  
 5) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION
  
 6) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  