| 2014-07-09 15:17:01 | BUILDING PLAN REVIEW |
| | PERMIT: 14061187 |
| | ADD: 900 FLORIDA AVE |
| | CONT: COASTAL CONSTRUCTION |
| | TEL: (561)630-3770 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: WED. JULY 09/2014 |
| | ACTION: DENIED |
| | |
| | 1) 0110 GA2.00 NOTES FOR FIRE PROTECTION ARE CONFUSING, |
| | IS OR IS NOT THIS STRUCTURE FIRE SPRINKLERED? |
| | TABLE 1016.1 300' FOR OPEN PARKING GARAGES |
| | NON-SPRINKLERED |
| | 1018.4 DEAD END EXC # 2 50 FT W/ FIRE SPRINKLERS |
| | 1014.3 COMMON PATH OF TRAVEL 50'-0" EXC # 8 PARKING |
| | GAGARES |
| | GFP1, GFP2 & GFP3 ONLY SHOW A DRY STAND PIPE SYSTEM. |
| | GFA-2 INDICATES THE INSTALATION OF A TAMPER & FLOW |
| | SWITCH. |
| | |
| | 2) 0150 GS0.00 INDICATES A GEOTECHNICAL SOILS |
| | ENGINEERING REPORT WAS COMPLETED ON 6/05/13. 2010 FBC-B |
| | 1803.3 BASIS OF INVESTIGATION. SOIL CLASSIFICATION |
| | SHALL BE BASED ON OBSERVATION AND ANY NECESSARY TESTS |
| | OF THE MATERIALS DISCLOSED BY BORINGS, TEST PITS OR |
| | OTHER SUBSURFACE EXPLORATION MADE IN APPROPRIATE |
| | LOCATIONS. ADDITIONAL STUDIES SHALL BE MADE AS |
| | NECESSARY TO EVALUATE SLOPE STABILITY, SOIL STRENGTH, |
| | POSITION AND ADEQUACY OF LOAD-BEARING SOILS, THE EFFECT |
| | OF MOISTURE VARIATION ON SOIL-BEARING CAPACITY, |
| | COMPRESSIBILITY, |
| | LIQUEFACTION AND EXPANSIVENESS. |
| | |
| | 3) THE PLANS SHOW STAIRS TO THE 2ND LEVEL BUT NO |
| | ELEVATOR. PLEASE SHOW COMPLIANCE WITH VERTICAL |
| | ACCESSIBILITY. 201.1.1 VERTICAL ACCESSIBILITY. SECTIONS |
| | 553.501-553.513, F.S., AND THE ADA STANDARDS FOR |
| | ACCESSIBLE DESIGN DO NOT RELIEVE THE OWNER OF ANY |
| | BUILDING, STRUCTURE OR FACILITY GOVERNED BY THOSE |
| | SECTIONS FROM THE DUTY TO PROVIDE VERTICAL |
| | ACCESSIBILITY TO ALL LEVELS ABOVE AND BELOW THE |
| | OCCUPIABLE GRADE LEVEL REGARDLESS OF WHETHER THE |
| | STANDARDS REQUIRE AN ELEVATOR TO BE INSTALLED IN SUCH |
| | BUILDING, STRUCTURE OR FACILITY. |
| | 553.509?VERTICAL ACCESSIBILITY.? |
| | (1)?THIS PART AND THE AMERICANS WITH DISABILITIES ACT |
| | STANDARDS FOR ACCESSIBLE DESIGN DO NOT RELIEVE THE |
| | OWNER OF ANY BUILDING, STRUCTURE, OR FACILITY GOVERNED |
| | BY THIS PART FROM THE DUTY TO PROVIDE VERTICAL |
| | ACCESSIBILITY TO ALL LEVELS ABOVE AND BELOW THE |
| | OCCUPIABLE GRADE LEVEL, REGARDLESS OF WHETHER THE |
| | STANDARDS REQUIRE AN ELEVATOR TO BE INSTALLED IN SUCH |
| | BUILDING, STRUCTURE, OR FACILITY, EXCEPT FOR: |
| | (A)?ELEVATOR PITS, ELEVATOR PENTHOUSES, MECHANICAL |
| | ROOMS, PIPING OR EQUIPMENT CATWALKS, AND AUTOMOBILE |
| | LUBRICATION AND MAINTENANCE PITS AND PLATFORMS. |
| | (B)?UNOCCUPIABLE SPACES, SUCH AS ROOMS, ENCLOSED |
| | SPACES, AND STORAGE SPACES THAT ARE NOT DESIGNED FOR |
| | HUMAN OCCUPANCY, FOR PUBLIC ACCOMMODATIONS, OR FOR WORK |
| | AREAS. |
| | (C)?OCCUPIABLE SPACES AND ROOMS THAT ARE NOT OPEN TO |
| | THE PUBLIC AND THAT HOUSE NO MORE THAN FIVE PERSONS, |
| | INCLUDING, BUT NOT LIMITED TO, EQUIPMENT CONTROL ROOMS |
| | AND PROJECTION BOOTHS. |
| | (D)?THEATERS, CONCERT HALLS, AND STADIUMS, OR OTHER |
| | LARGE ASSEMBLY AREAS THAT HAVE STADIUM-STYLE SEATING OR |
| | TIERED SEATING IF SS. 221 AND 802 OF THE STANDARDS ARE |
| | MET. |
| | (E)?ALL PLAY AND RECREATION AREAS IF THE REQUIREMENTS |
| | OF CHAPTER 10 OF THE STANDARDS ARE MET. |
| | (F)?ALL EMPLOYEE AREAS AS EXEMPTED IN S. 203.9 OF THE |
| | STANDARDS. |
| | (G)?FACILITIES, SITES, AND SPACES EXEMPTED BY S. 203 OF |
| | THE STANDARDS. |
| | (2)?HOWEVER, BUILDINGS, STRUCTURES, AND FACILITIES |
| | MUST, AS A MINIMUM, COMPLY WITH THE AMERICANS WITH |
| | DISABILITIES ACT STANDARDS FOR ACCESSIBLE DESIGN. |
| | |
| | 4A) SHEET GA8.00 NOTE # 27 FIXED CANVAS CANOPY, THERE |
| | IS NO WIND DESIGN CRITERIA FOR THIS PRODUCT NOR IS |
| | THERE . 2010 FBC-B 3102.7 ENGINEERING DESIGN. THE |
| | STRUCTURE SHALL BE DESIGNED AND CONSTRUCTED TO SUSTAIN |
| | DEAD LOADS; LOADS DUE TO TENSION OR INFLATION; AND LIVE |
| | LOADS INCLUDING WIND LOADS AND FLOOD IN ACCORDANCE WITH |
| | CHAPTER 16. |
| | |
| | 4B) THE FIXED CANVAS CANOPY IS ONTOP OF A BUILDING TYPE |
| | I-B PLEASE INDICATE HOW COMPLIANCE WITH THE FOLLOWING: |
| | 2010 FBC-B 3102.6 MIXED CONSTRUCTION. |
| | MEMBRANE STRUCTURES SHALL BE PERMITTED TO BE UTILIZED |
| | AS SPECIFIED IN THIS SECTION AS A PORTION OF BUILDINGS |
| | OF OTHER TYPES OF CONSTRUCTION. HEIGHT AND AREA LIMITS |
| | SHALL BE AS SPECIFIED FOR THE TYPE OF CONSTRUCTION AND |
| | OCCUPANCY OF THE BUILDING. |
| | |
| | 3102.6.1 NONCOMBUSTIBLE MEMBRANE. |
| | A NONCOMBUSTIBLE MEMBRANE SHALL BE PERMITTED FOR USE AS |
| | THE ROOF OR AS A SKYLIGHT OF ANY BUILDING OR ATRIUM OF |
| | A BUILDING OF ANY TYPE OF CONSTRUCTION PROVIDED IT IS |
| | AT LEAST 20 FEET (6096 MM) ABOVE ANY FLOOR, BALCONY OR |
| | GALLERY. |
| | |
| | 3102.6.1.1 MEMBRANE. |
| | A MEMBRANE MEETING THE FIRE PROPAGATION PERFORMANCE |
| | CRITERIA OF NFPA 701 SHALL BE PERMITTED TO BE USED AS |
| | THE ROOF OR AS A SKYLIGHT ON BUILDINGS OF TYPES IIB, |
| | III, IV AND V CONSTRUCTION, PROVIDED IT IS AT LEAST 20 |
| | FEET (6096 MM) ABOVE ANY FLOOR, BALCONY OR GALLERY. |
| | |
| | 4C) SHEET GA8.00 NOTE # 31 CABLE GUARDRAIL, GUARDRAILS |
| | TO REJECT A 4 INCH SPHERE. PLEASE PROVIDE AT WHAT |
| | CENTERS THE CABLE WILL NEED TO BE, CENTER TO CENTER ON |
| | POST AND AT WHAT TENSION IT WILL TAKE TO KEEP THE |
| | SPHERE FROM GOING THROUGH THE SPACING OF THE CABLES. |
| | 2010 FBC-B 1013.3. |
| | |
| | 4D)(1) SHEET GA8.00 NOTE # 31 CABLE GUARDRAIL, |
| | GUARDRAILS ALSO INDICATE A FABRIC SCREEN TO BE ATTACHED |
| | TO THE GUARDRAIL SYSTEM, PLEASE PROVIDE INFORMATION ON |
| | FABRIC, COMPLIANCE WITH FIRE PROPAGATION PERFORMANCE |
| | CRITERIA OF NFPA 701. |
| | |
| | 4D)(2) SHEET GA8.00 NOTE # 31 CABLE GUARDRAIL, |
| | GUARDRAILS ALSO INDICATE A FABRIC SCREEN TO BE ATTACHED |
| | TO THE GUARDRAIL SYSTEM, |
| | SHOW COMPLIANCE WITH : 3102.7 ENGINEERING DESIGN. |
| | THE STRUCTURE SHALL BE DESIGNED AND CONSTRUCTED TO |
| | SUSTAIN DEAD LOADS; LOADS DUE TO TENSION OR INFLATION; |
| | AND LIVE LOADS INCLUDING WIND LOADS IN ACCORDANCE WITH |
| | CHAPTER 16. |
| | |
| | 4E) PLEASE PROVIDE COMPLIANCE WITH 2010 FBC-B 1607.7.3 |
| | VEHICLE BARRIER SYSTEMS FOR THE 2ND FLOOR AND RAMP. |
| | |
| | 5) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| | PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| | A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| | APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION |
| | |
| | 6) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |
| | |
| | |
| | |