| Plan Review Notes For Permit 14061136 |
| Permit Number |
14061136 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2014-07-16 17:22:50 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | 1. SEE OPENING #1. SPAN IS SHOWN AS 108" (9'). SEE | | | SHEET 10. CONCRETE SUBSTRATE ON THE TOP, CONNECTION | | | TYPE C3, ELCO ULTRACON, 9' SPAN, 62PSF, CANNOT BE USED | | | (BOX IS HATCHED). | | | | | | CONTRACTOR HAS HIGHLIGHTED THE ROW FOR 48PSF, BUT | | | DESIGN PRESSURE PROPOSED FOR THIS OPENING IS 49.4, SO | | | THE NEXT ROW (62PSF) MUST BE USED. | | | | | | 2. SEE OPENING #1, BOTTOM AND CHART ON SHEET 11. FOR | | | CONCRETE BLOCK, ULTRACON, CONNECTION TYPE C3, IS | | | HATCHED (CANNOT BE USED) FOR 62 PSF. | | | | | | 3. REVISE INSTALLATION SCHEDULE TO BE MORE SPECIFIC | | | REGARDING THE FASTENER. THERE ARE DIFFERENT DIAMETER OF | | | ELCO ULTRACON. | | | | | | CHECK ALL OPENINGS AS THE ONE GIVEN IS ONLY ONE | | | EXAMPLE. THE OTHER OPENINGS HAVE THE SAME ISSUE. |
|