Plan Review Notes
Plan Review Notes For Permit 14061136
Permit Number 14061136
Review Stop B
Sequence Number 2
Notes
Date Text
2014-07-16 17:22:50****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. SEE OPENING #1. SPAN IS SHOWN AS 108" (9'). SEE
 SHEET 10. CONCRETE SUBSTRATE ON THE TOP, CONNECTION
 TYPE C3, ELCO ULTRACON, 9' SPAN, 62PSF, CANNOT BE USED
 (BOX IS HATCHED).
  
 CONTRACTOR HAS HIGHLIGHTED THE ROW FOR 48PSF, BUT
 DESIGN PRESSURE PROPOSED FOR THIS OPENING IS 49.4, SO
 THE NEXT ROW (62PSF) MUST BE USED.
  
 2. SEE OPENING #1, BOTTOM AND CHART ON SHEET 11. FOR
 CONCRETE BLOCK, ULTRACON, CONNECTION TYPE C3, IS
 HATCHED (CANNOT BE USED) FOR 62 PSF.
  
 3. REVISE INSTALLATION SCHEDULE TO BE MORE SPECIFIC
 REGARDING THE FASTENER. THERE ARE DIFFERENT DIAMETER OF
 ELCO ULTRACON.
  
 CHECK ALL OPENINGS AS THE ONE GIVEN IS ONLY ONE
 EXAMPLE. THE OTHER OPENINGS HAVE THE SAME ISSUE.