 PROJECT: VALLY FORGE RESIDENCE
 PERMIT#: 14061120
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 2ND ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) REVISE THE RISER DIAGRAM TO INCLUDE THE FEED TO THE
 PANEL IN THE GARAGEANY POWER IN THE SHED BUILDING AND
 TO INDICATE THE NEW PANEL IS NEMA 3R APPROVED FOR USE
 OUTDOORS.
  
 2) PROVIDE ELECTRICAL PANEL SCHEDULE FOR BOTH
 ELECTRICAL PANELS.
  
 3) VERIFY THE EXISTANCE OR THE INSTALLATION OF SMOKE/CO
 DETECTORS IN COMPLIANCE WITH THE FBC -R 314, 315
  
 4) PROVIDE CIRCUITING ON THE FLOOR PLAN THAT COINCIDES
 WITH THE PANEL SCHEDULES TO BE PROVIDED.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO
 SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED
 SHEETS FOR COMPARATIVE REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  