| Plan Review Notes For Permit 14061120 |
| Permit Number |
14061120 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2014-11-20 16:32:12 | PLAN REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC 2010 | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | BUILDING | | | | | | 1) PLAN SHEETS A.03 AND A.05 ARE MISSING FROM ONE SET | | | OF THE PLANS. SUBMIT ADDITIONAL SHEETS A.03 AND A.05. | | | FBC 107.1 | | | | | | 2) THE RAS 117 CALCULATIONS THAT WERE SUBMITTED FOR THE | | | GAF MODIFIED ROOF SYSTEM, NOA NO. 13-0424.14 ARE NOT | | | ACCEPTABLE. THERE ARE THREE DIFFERENT FASTENING OPTIONS | | | WITH A MAXIMUM DESIGN PRESSURE OF -60 PSF. SPECIFY THE | | | FASTENER AS WELL AS THE LAP AND FIELD SPACING FOR THE | | | ANCHOR SHEET. THE NOTE ON PAGE 8 STATE THAT THE | | | INSULATION IS ADHERED TO THE ANCHOR SHEET WITH HOT | | | ASPHALT. SHOW ALL OF THE RAS 117 CALCULATIONS THAT WERE | | | USED TO DETERMINE THE ENHANCED FASTENER SPACING. IT IS | | | UNCLEAR WHY THE NUMBER OF INSULATION BOARD FASTENERS | | | WAS PROVIDED. FBC 107.2.1.4 | | | | | | 3) SHOW COMPLIANCE WITH 2010 FBC ENERGY CONSERVATION | | | SECT. 101.4.3 & 103.2 BY SUBMITTING THE PROPER | | | CONSTRUCTION DOCUMENTS. SEE RESIDENTIAL BUILDING FORMS | | | 402 OR 405. | | | | | | |
|