| Plan Review Notes For Permit 14061120 |
| Permit Number |
14061120 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-07-14 15:37:27 | 2010 FBC | | | | | | DENIED BY MECHANICAL | | | | | | 1) NO MECHANICAL PLANS WERE SUBMITTED. SUBMIT TWO SETS | | | OF MECHANICAL PLANS. SPECIFY THE DUCT SIZES AND | | | LOCATIONS. SPECIFY THE GRILL LOCATIONS, SIZES AND CFMS | | | AT EACH OUTLET. CITY AMENDMENTS 107.3.5.3 | | | | | | 2) SHOW COMPLIANCE WITH FBCR M1602.4 FOR BALANCED | | | RETURN AIR. | | | | | | 3) SUBMIT TWO SETS OF HEATING AND COOLING EQUIPMENT | | | SIZING CALCULATIONS AS REQUIRED BY FBCR M1401.3. | | | | | | 4) PROVIDE AN EQUIPMENT SCHEDULE ON THE MECHANICAL | | | PLANS THAT MATCHES THE EQUIPMENT SIZING CALCULATIONS. | | | CITY AMENDMENTS 107.2.1 | | | | | | 5) THE NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR | | | THE DESIGN IS REQUIRED ON THE PLANS. CITY AMENDMENTS | | | 107.2.1 | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|