Plan Review Notes
Plan Review Notes For Permit 14061120
Permit Number 14061120
Review Stop B
Sequence Number 1
Notes
Date Text
2014-07-14 18:21:492010 FBC
  
 DENIED BY BUILDING
  
 1) THE WIND DESIGN DATA IN THE WIND PRESSURE SCHEDULE
 ON SHEET A.07 IS INCORRECTLY SPECIFIED AS 140 MPH AND
 THE PRESSURES ARE INCORRECT. THE WINDSPEED FOR THIS
 PROJECT IS 170 MPH AND THE EXPOSURE CATEGORY IS C. THE
 WIND SPEED IS SPECIFIED AS 170 MPH AND EXPOSURE D ON
 SEVERAL OF THE PLAN SHEETS. PLEASE CORRECT AND SPECIFY
 THE WIND PRESSURES FOR THE CORRESPONDING WINDSPEED,
 ROOF HEIGHT AND EXPOSURE CATEGORY. FBCR 301.2.1
  
 2) THE APPLICABLE EDITION OF THE NATIONAL ELECTRICAL
 CODE ( NEC) IS THE 2008. THE APPLICABLE EDITION OF THE
 FLORIDA FIRE PREVENTION CODE IS THE 2010 EDITION. THIS
 IS LISTED ON SEVERAL OF THE PLAN SHEETS. IT IS CORRECT
 ON SOME AND NOT ON OTHERS. PLEASE CORRECT.
  
 3) SUBMIT TWO SETS OF ENERGY COMPLIANCE DOCUMENTS AS
 REQUIRED BY FBC ENERGY CONSERVATION SECTION 103.
  
 4) THERE ARE CONFLICTING NOTES REGARDING THE ATTIC
 INSULATION. WALL SECTION C ON A.07 HAS A NOTE
 SPECIFYING R-30 INSULATION WITH AN ARROW POINTING TO
 THE BOTTOM CORD OF THE TRUSS, HOWEVER, THE INSULATION
 IS SHOWN ON THE TOP CORD. A NOTE ON SHEET A.04
 SPECIFIES SPRAY FOAM INSULATION ON THE TOP CORD. THERE
 ARE ROOF VENT CALCULATIONS AND OFF RIDGE ROOF VENTS
 SHOWN ON SHEET A.06. THE SPRAY FOAM ON THE UNDER SIDE
 OF THE ROOF DECK IS TYPICALLY USED WITH UN-VENTED
 ATTICS, AS THE ATTIC IS CONSIDERED CONDITIONED SPACE
 WITH THIS APPLICATION. PLEASE CLARIFY AND COORDINATE
 THE INFORMATION ON THE PLANS. CITY AMENDMENTS 107.2.1
  
 5) SUBMIT TWO COPIES OF THE EVALUATION REPORT FOR THE
 SPRAY FOAM INSULATION THAT WILL BE INSTALLED. FBCR 316.
  
 6) ON SHEET A.07 THE DETAILS FOR THE EXTERIOR WINDOW
 HEAD, SILL AND JAMB SHOW LATH AND PLASTER (STUCCO) AND
 NOT THE CEMENTITIOUS SIDING THAT IS SPECIFIED ON THE
 OTHER PLAN SHEETS. PLEASE CORRECT. CITY AMENDMENTS
 107.2.1
  
 7) ON SHEET A.08, SOME OF THE ID TAGS ON THE FOUNDATION
 PLAN DO NOT MATCH THE DETAILS OR THE DETAILS ARE
 MISSING. THERE ARE TWO DIFFERENT DETAILS NUMBERED 2 AND
 TWO MORE NUMBERED 6. THERE WERE ALSO TWO PLAN SHEETS
 NUMBERED A.08 IN BOTH OF THE PLAN SETS THAT WERE
 SUBMITTED. PLEASE REVIEW PLANS FOR ACCURACY AND
 CONSISTENCY, THEN MAKE CORRECTIONS. CITY AMENDMENTS
 107.2.1
  
 8) ON SHEET A.08, THE ELEVATION FOR THE TOP OF THE SLAB
 AT THE LOGGIA INDICATES THAT IT IS 4" HIGHER THAN THE
 HOUSE SLAB. THERE IS A NOTE THAT INDICATES THERE IS A
 6" STEP DOWN. PLEASE CORRECT. CITY AMENDMENTS 107.2.1
  
 9) THERE IS A 6" STEP DOWN AND A 6" WHEEL STOP SHOWN IN
 THE GARAGE ON SHEET A.04. THE FOUNDATION PLAN ON A.08,
 DOES NOT SHOW THE 6" INCH WHEEL STOP. PLEASE CLARIFY.
 CITY AMENDMENTS 107.2.1
  
 10) PROVIDE A STRUCTURAL DETAIL VIEW OF THE 4 X 6 WOOD
 POSTS' TOP AND BOTTOM CONNECTIONS. FBCR 301.1
  
 11) SUBMIT THE MANUFACTURER'S INSTALLATION GUIDE AND
 SPAN TABLES FOR THE LAMINATED VENEER LUMBER BEAMS. FBCR
 301.1 & R602.1.1.2
  
 12) THE DESIGN PRESSURES FOR THE CLOPAY OVERHEAD GARAGE
 DOOR, FL 15279 ARE LOWER THAN THE REQUIRED WIND LOAD
 PRESSURES FOR THE END ZONE OF A TWO STORY STRUCTURE
 LOCATED IN EXPOSURE D OR C WITH A 170 MPH VULT WIND
 SPEED.
  
 13) SUBMIT TWO COPIES OF THE PRODUCT APPROVALS FOR THE
 EXTERIOR CEMENTITIOUS SIDING AND THE STRUCTURAL
 MULLIONS AS REQUIRED BY DCA RULE 9N-3.
  
 14) SPECIFY THE APPROVED SYSTEM AND THE FASTENING
 OPTION THAT WILL BE USED FOR THE GAF RUBEROID MODIFIED
 BITUMEN SYSTEM, NOA NO. 13-0424.14. SUBMIT TWO SETS OF
 SIGNED AND SEALED RAS 117 CALCULATIONS FOR ENHANCED
 FASTENING AT THE PERIMETER AND CORNER AREAS AS REQUIRED
 BY LIMITATION #7 OF THE NOA. CITY AMENDMENTS 107.2.1 &
 FBCR 301.2.1
  
 15) IN ORDER TO SPEED PLAN REVIEW, PLEASE SUBMIT A
 RESPONSE LETTER INDICATING HOW EACH OF THE REVIEW ITEMS
 HAS BEEN ADDRESSED.
  