| Plan Review Notes For Permit 14060946 |
| Permit Number |
14060946 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2014-10-11 09:28:47 | 2010 FBC / 2008 NEC | | | | | | DENIED BY ELECTRIC | | | | | | 1) FBC- 107.3.5.3 - PROVIDE AN ELECTRIC SERVICE RISER | | | DIAGRAM WITH WIRE SIZES, CONDUIT DETAIL AND GROUNDING | | | DETAIL. | | | | | | 2) SHOW COMPLIANCE WITH NEC 250.50 WHICH REQUIRES ALL | | | ELECTRODES THAT ARE PRESENT TO BE BONDED. | | | | | | 3) SHOW COMPLIANCE WITH NEC 250.94 FOR INTER-SYSTEM | | | BONDING. | | | | | | 4) SHOW COMPLIANCE WITH NEC 210.52 FOR RECEPTACLE | | | OUTLET SPACING. THE RECEPTACLE SPACING IN THE DEN NEEDS | | | TO BE SUCH THAT NO POINT MEASURED HORIZONTALLY ALONG | | | THE FLOOR LINE IN ANY WALL SPACE IS MORE THAN 6 FEET | | | FROM A RECEPTACLE. | | | | | | 5) NEC 210.12 (B) - OUTLETS TO BE AFCI PROTECTED. | | | | | | 6) NEC 406.11 - TAMPER-RESISTANT RECEPTACLES ARE | | | REQUIRED. | | | | | | 7) NEC 250.56 - SERVICE GROUNDING ELECTRODE TO BE | | | AUGMENTED BY AN ADDITIONAL ELECTRODE 6 FEET AWAY OR | | | PROVIDE EVIDENCE OF RESISTANCE TO GROUND OF 25 OHMS OR | | | LESS. | | | | | | 8) NEC 110.9 - SPECIFY THE A.I.C. RATING OF THE | | | ELECTRICAL EQUIPMENT ON THE PLANS. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|