| 2014-07-14 07:01:57 | 2010 FBC / 2008 NEC |
| | |
| | DENIED BY ELECTRIC |
| | |
| | 1) SHOW COMPLIANCE WITH FBCR 314.3.1. WHEN ALTERATIONS, |
| | REPAIRS OR ADDITIONS REQUIRING A PERMIT OCCUR, THE |
| | DWELLING SHALL BE EQUIPPED WITH SMOKE ALARMS AS |
| | REQUIRED FOR NEW DWELLINGS. |
| | |
| | 2) SHOW COMPLIANCE WITH NEC 250.50 WHICH REQUIRES ALL |
| | ELECTRODES THAT ARE PRESENT TO BE BONDED. |
| | |
| | 3) SHOW COMPLIANCE WITH NEC 250.94 FOR INTER-SYSTEM |
| | BONDING. |
| | |
| | 4) SHOW COMPLIANCE WITH NEC 210.52 FOR RECEPTACLE |
| | OUTLET SPACING. THE WALL SPACES THAT ARE 2 FT OR MORE |
| | IN WIDTH BETWEEN THE DOORS IN THE MASTER BEDROOM AND |
| | BEDROOM #2 ARE REQUIRED TO HAVE A RECEPTACLE. ALSO THE |
| | RECEPTACLE SPACING IN THE NEW FAMILY ROOM NEEDS TO BE |
| | SUCH THAT NO POINT MEASURED HORIZONTALLY ALONG THE |
| | FLOOR LINE IN ANY WALL SPACE IS MORE THAN 6 FEET FROM A |
| | RECEPTACLE. |
| | |
| | 5) SHOW COMPLIANCE WITH NEC 210.52 (E)(1) WHICH |
| | REQUIRES A RECEPTACLE AT THE FRONT AND REAR OF THE |
| | DWELLING. |
| | |
| | 6) SHOW COMPLIANCE WITH NEC 210.63 FOR THE REQUIRED |
| | HEATING AND A/C RECEPTACLE FOR THE SERVICING OF THE A/C |
| | CONDENSING UNIT AT THE EXTERIOR OF THE DWELLING. |
| | |
| | 7) SHOW COMPLIANCE WITH NEC 210.8(B) FOR GROUND FAULT |
| | CIRCUIT- INTERRUPTER PROTECTION FOR OUTDOOR RECEPTACLES |
| | AND NEC 406.8 FOR WEATHER PROTECTION OF RECEPTACLES IN |
| | WET LOCATIONS. |
| | |
| | 8) THE NAME AND SIGNATURE OF THE PERSON THAT IS |
| | RESPONSIBLE FOR THE DESIGN IS REQUIRED ON THE |
| | ELECTRICAL PLANS. CITY AMENDMENTS 107.2.1 |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)805-6714 |
| | [email protected] |