| Plan Review Notes For Permit 14060942 |
| Permit Number |
14060942 |
|
| Review Stop |
B |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2014-08-25 07:45:00 | 2010 FBC | | | | | | DENIED BY BUILDING | | | | | | 1) THE ROOFING INFORMATION THAT WAS SUBMITTED IS NOT | | | CORRECT. THE PLANS SHOW AN INSULATED FLAT ROOF. THE | | | SYSTEM THAT WAS SELECTED IS FOR A NON-INSULATED DECK. | | | THE RAS 117 ENHANCED FASTENING CALCULATIONS THAT WERE | | | SUBMITTED ARE FOR MECHANICALLY FASTENED INSULATION, | | | HOWEVER, NONE OF THE INSULATED SYSTEMS IN NOA NO. | | | 14-0224.03 HAVE MECHANICALLY FASTENED INSULATION. ONLY | | | THE ANCHOR SHEET NEEDS ENHANCED FASTENING. THE | | | INSULATION IS ADHERED TO THE ANCHOR SHEET WITH HOT | | | ASPHALT. I'LL LET YOU KNOW IF THERE IS ANY THING ELSE | | | THAT NEEDS TO BE CORRECTED. PLEASE CORRECT. CITY | | | AMENDMENTS 107.2.1 | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|