| 2014-07-10 16:08:47 | 2010 FBC | | | | | | DENIED BY BUILDING | | | | | | 1) THIS STRUCTURE IS LOCATED IN AN A5 FLOOD ZONE. THE | | | ELEVATION CERTIFICATE THAT WAS SUBMITTED INDICATES THAT | | | THE STRUCTURE AND GARAGE ARE BOTH ABOVE THE REQUIRED | | | MINIMUM OF 7.5 FEET NGVD. HOWEVER, IT ALSO SHOWS THAT | | | SOME OF THE EQUIPMENT THAT SERVICES THE BUILDING IS TOO | | | LOW. THIS WILL NEED TO BE CORRECTED AND A NEW ELEVATION | | | CERTIFICATE SHOWING COMPLIANCE IS REQUIRED PRIOR TO | | | RECIEVING FINAL INSPECTION APPROVAL. CITY OF WEST PALM | | | BEACH FLOOD ORDINANCE. | | | | | | 2) THE PLANS SHOW A DUAL FUEL GRIDDLE AND RANGE. PLEASE | | | CALARIFY THE TYPE OF FUEL THAT THIS APPLIANCE WILL USE. | | | IF IT USES NATURAL OR LP GAS A SEPARATE PERMIT, | | | APPLICATION AND REVIEW OF THE GAS RISER PLAN WILL BE | | | REQUIRED. | | | | | | 3) SHOW COMPLIANCE WITH FBCR 315 FOR CARBON MONOXIDE | | | ALARMS. | | | | | | 4) FBCR 803.2.3.1 REQUIRES THE ROOF SHEATHING TO BE | | | FASTENED WITH 8D RING SHANK NAILS. PLEASE CORRECT NOTES | | | ON SHEET A4. | | | | | | 5) SUBMIT TWO SETS OF ENERGY COMPLIANCE DOCUMENTS AS | | | REQUIRED BY FBC ENERGY CONSERVATION SECTION 103.2 | | | | | | 6) SUBMIT TWO SETS OF PRODUCT APPROVALS FOR THE ROOFING | | | MATERIAL AS REQUIRED BY DCA RULE 9N-3. | | | | | | 7) THE PRODUCT APPROVALS ARE REQUIRED TO BE REVIEWED | | | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. CITY | | | AMENDMENTS 107.3.4.1 | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|