| Plan Review Notes For Permit 14060881 |
| Permit Number |
14060881 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-08-30 09:58:11 | BUILDING PROVISO: BEDROOMS MUST MEET THESE | | | REQUIREMENTS: | | | | | | R310.1 EMERGENCY ESCAPE AND RESCUE REQUIRED. | | | R310.1.1 MINIMUM OPENING AREA. ALL EMERGENCY ESCAPE AND | | | RESCUE OPENINGS SHALL HAVE A MINIMUM NET CLEAR OPENING | | | OF 5.7 SQUARE FEET. | | | EXCEPTION: GRADE FLOOR OPENINGS SHALL HAVE A MINIMUM | | | NET CLEAR OPENING OF 5 SQUARE FEET (0.465 M2). | | | R310.1.2 MINIMUM OPENING HEIGHT. THE MINIMUM NET CLEAR | | | OPENING HEIGHT SHALL BE 24 INCHES (610 MM). | | | R310.1.3 MINIMUM OPENING WIDTH. THE MINIMUM NET CLEAR | | | OPENING WIDTH SHALL BE 20 INCHES (508 MM). | | | R313.3 SMOKE ALARMS. LOCATION | | | SMOKE ALARMS SHALL BE INSTALLED IN THE FOLLOWING | | | LOCATIONS: | | | 1. IN EACH SLEEPING ROOM. | | | 2. OUTSIDE EACH SEPARATE SLEEPING AREA IN THE IMMEDIATE | | | VICINITY OF THE BEDROOMS. | | | | | | | | 2014-06-20 14:24:39 | MASTER PERMIT #14050971 BUILDING REVIEW BY SHILL |
|