| 2014-12-01 11:54:48 | DATE: 12/1/2014 |
| | PROJECT: UTILITY STRUCTURE RENNOVATION |
| | PERMIT#: 14060869 |
| | CODE: 2008 EDITION OF THE NEC |
| | 2010 EDITION OF THE FBC |
| | 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| | ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| | |
| | 3RD ELECTRICAL PLAN REVIEW |
| | ACTION: DENIED |
| | |
| | 1) INDICATE SITE PLAN THE LOCATION OF THE ELECTRICAL |
| | SERVICE WITH 200AMP MAIN (PANEL), THE HOUSE PANEL, AND |
| | TANKLESS WATER HEATER, |
| | |
| | 2) PROVIDE A COMPLETE LOAD CALCULATION. LOADS FOR NEW |
| | CIRCUITS OR EXTENDED CIRCUITS IN PREVIOUSLY WIRED |
| | DWELLING UNITS SHALL BE CALCULATED IN ACCORDANCE WITH |
| | NEC 220.12 OR 220.14, AS APPLICABLE. NEC 220.40, NEC |
| | 220.16(2) |
| | |
| | 3) EVERY CIRCUIT AND CIRCUIT MODIFICATION IN THE PANEL |
| | SCHEDULE SHALL BE LEGIBLY IDENTIFIED AS TO ITS CLEAR, |
| | EVIDENT, AND SPECIFIC PURPOSE OR USE. ADD CIRCUIT IN |
| | THE SUB-PANEL TO IDENTIFY THE A/C CU. NEC 408.4, |
| | |
| | 4) REVISE THE RISER DIAGRAM TO INDICATE HOW THE 150AMP |
| | HOUSE PANEL, THE 125AMP UTILITY RM PANEL, AND NOW THE |
| | TANKLESS WATER HEATER ARE FED. |
| | |
| | 5) REVISE THE RISER DIAGRAM TO INDICATE THE CORRECT |
| | SIZED CONDUCTORS ARE IN THE SERVICE RISER MAST AND |
| | NIPPLE TO THE "MAIN"(PANEL) ARE APPROVED FOR THE TOTAL |
| | CONNECTED LOAD TO BE SERVED. THE CONDUCTOR SIZES |
| | CURRENTLY INDICATED ON THE RISER DIAGRAM ARE NOT |
| | APPROVED FOR THE LOAD TO BE SERVED. |
| | |
| | 6) INDICATE THE LOCATION AND MEANS OF DISCONNECT FOR |
| | THE TANKLESS WATER HEATER, A/C CU, AND AHU. NEC 422.31, |
| | WPB AMENDMENTS TO FBC 107.3.2 |
| | |
| | 7) REVISE THE FLOOR PLAN TO INCLUDE THE CIRCUIT NUMBERS |
| | TO COINCIDE WITH THE PANEL SCHEDULE. ADD THE CIRCUIT |
| | FOR THE A/C, CU AND THE TANKLESSS WATER HEATER. FBC- 1 |
| | 07.3.5.3 |
| | |
| | 8) VERIFY THE FLOOR PLAN TO INDICATE RECEPTACLE OUTLETS |
| | ARE INSTALLED AT EACH KITCHEN COUNTERTOP SPACE THAT IS |
| | 12" OR WIDER. RECEPTACLE OUTLETS SHALL BE INSTALLED SO |
| | THAT NO POINT ALONG THE WALL LINE IS MORE THAN 24" |
| | MEASURED HORIZONTALLY FROM A RECEPTACLE OUTLET IN THAT |
| | SPACE. RECEPTACLES SHALL BE INSTALLED SUCH THAT NO |
| | POINT MEASURED HORIZONTALLY ALONG THE FLOOR LINE IN ANY |
| | WALL SPACE IS MORE THAN (6 FT) FROM A RECEPTACLE |
| | OUTLET. NEC 210.52(C)(1) |
| | |
| | 9) ALL NEW GENERAL PURPOSE OUTLETS MUST BE TAMPER |
| | RESISTANT AND AFCI PROTECTED. NEC 210.12, 406.11 |
| | |
| | 11) A BONDING STRIP IS REQUIRED AT SERVICE GROUND. NEC |
| | 250.94 |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. SEE LINK: |
| | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| | 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| | |
| | ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED |
| | PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE |
| | PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE |
| | REVIEW. |
| | |
| | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| | 561-805-6717 OR [email protected] |
| | |