2014-12-01 11:54:48DATE: 12/1/2014
 PROJECT: UTILITY STRUCTURE RENNOVATION
 PERMIT#: 14060869
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 3RD ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) INDICATE SITE PLAN THE LOCATION OF THE ELECTRICAL
 SERVICE WITH 200AMP MAIN (PANEL), THE HOUSE PANEL, AND
 TANKLESS WATER HEATER,
  
 2) PROVIDE A COMPLETE LOAD CALCULATION. LOADS FOR NEW
 CIRCUITS OR EXTENDED CIRCUITS IN PREVIOUSLY WIRED
 DWELLING UNITS SHALL BE CALCULATED IN ACCORDANCE WITH
 NEC 220.12 OR 220.14, AS APPLICABLE. NEC 220.40, NEC
 220.16(2)
  
 3) EVERY CIRCUIT AND CIRCUIT MODIFICATION IN THE PANEL
 SCHEDULE SHALL BE LEGIBLY IDENTIFIED AS TO ITS CLEAR,
 EVIDENT, AND SPECIFIC PURPOSE OR USE. ADD CIRCUIT IN
 THE SUB-PANEL TO IDENTIFY THE A/C CU. NEC 408.4,
  
 4) REVISE THE RISER DIAGRAM TO INDICATE HOW THE 150AMP
 HOUSE PANEL, THE 125AMP UTILITY RM PANEL, AND NOW THE
 TANKLESS WATER HEATER ARE FED.
  
 5) REVISE THE RISER DIAGRAM TO INDICATE THE CORRECT
 SIZED CONDUCTORS ARE IN THE SERVICE RISER MAST AND
 NIPPLE TO THE "MAIN"(PANEL) ARE APPROVED FOR THE TOTAL
 CONNECTED LOAD TO BE SERVED. THE CONDUCTOR SIZES
 CURRENTLY INDICATED ON THE RISER DIAGRAM ARE NOT
 APPROVED FOR THE LOAD TO BE SERVED.
  
 6) INDICATE THE LOCATION AND MEANS OF DISCONNECT FOR
 THE TANKLESS WATER HEATER, A/C CU, AND AHU. NEC 422.31,
 WPB AMENDMENTS TO FBC 107.3.2
  
 7) REVISE THE FLOOR PLAN TO INCLUDE THE CIRCUIT NUMBERS
 TO COINCIDE WITH THE PANEL SCHEDULE. ADD THE CIRCUIT
 FOR THE A/C, CU AND THE TANKLESSS WATER HEATER. FBC- 1
 07.3.5.3
  
 8) VERIFY THE FLOOR PLAN TO INDICATE RECEPTACLE OUTLETS
 ARE INSTALLED AT EACH KITCHEN COUNTERTOP SPACE THAT IS
 12" OR WIDER. RECEPTACLE OUTLETS SHALL BE INSTALLED SO
 THAT NO POINT ALONG THE WALL LINE IS MORE THAN 24"
 MEASURED HORIZONTALLY FROM A RECEPTACLE OUTLET IN THAT
 SPACE. RECEPTACLES SHALL BE INSTALLED SUCH THAT NO
 POINT MEASURED HORIZONTALLY ALONG THE FLOOR LINE IN ANY
 WALL SPACE IS MORE THAN (6 FT) FROM A RECEPTACLE
 OUTLET. NEC 210.52(C)(1)
  
 9) ALL NEW GENERAL PURPOSE OUTLETS MUST BE TAMPER
 RESISTANT AND AFCI PROTECTED. NEC 210.12, 406.11
  
 11) A BONDING STRIP IS REQUIRED AT SERVICE GROUND. NEC
 250.94
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED
 PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE
 PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE
 REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  