| 2014-09-18 08:03:51 | DATE: 9/18/2014 |
| | PROJECT: UTILITY STRUCTURE RENNOVATION |
| | PERMIT#: 14060869 |
| | CODE: 2008 EDITION OF THE NEC |
| | 2010 EDITION OF THE FBC |
| | 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| | ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| | |
| | 1ST ELECTRICAL PLAN REVIEW |
| | ACTION: DENIED |
| | |
| | 1) THE TOTAL KW LOAD INDICATED AT THE UTILLITY RM SUB |
| | PANEL IS 35.4KW WHICH WOULD BE THE EQUIVILANT OF |
| | 147AMPS NOT 90 AMPS AS INDICATED AT THE RISER DIAGRAM, |
| | THE CALCULATED LOAD OF A FEEDER OR SERVICE SHALL NOT BE |
| | LESS THAN THE SUM OF THE LOADS ON THE BRANCH CIRCUITS |
| | SUPPLIED, AS DETERMINED BY PART II OF THIS ARTICLE, |
| | AFTER ANY APPLICABLE DEMAND FACTORS PERMITTED BY PART |
| | III OR IV OR REQUIRED BY PART V HAVE BEEN APPLIED. NEC |
| | 220.40 |
| | PROVIDE A COMPLETE LOAD CALCULATION ON THE UTILITY |
| | STRUCTURE AND ON THE WHOLE ELECTRICAL SERVICE INCLUDING |
| | THE MAIN HOUSE. PROVIDE A PANEL SCHEDULE SHOWING ALL |
| | LOADS BALANCED. INDICATE THE PROPOSED WIRING METHOD, |
| | WIRE SIZE WITH OVER CURRENT PROTECTION FOR ALL |
| | CIRCUITS. NEC 215.5, 220.12, 220.40, 230.31 |
| | |
| | 2) THE ELECTRICAL SERVICE RISER DIAGRAM NEEDS TO BE |
| | REVISED TO INDICATE HOW THE TRANSITION IS MADE FROM THE |
| | 200AMP MAIN BREAKER AT THE HOUSE TO FEED THE 150AMP |
| | HOUSE PANEL AND THE 125AMP UTILITY RM PANEL. |
| | |
| | 3) INDICATE THE LOCATION AND MEANS OF DISCONNECT FOR |
| | THE ELECTRIC WATER HEATER, AND A/C AHU. NEC 422.31, WPB |
| | AMENDMENTS TO FBC 107.3.2 |
| | |
| | 5) A BONDING STRIP IS REQUIRED AT SERVICE GROUND. NEC |
| | 250.94 |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. SEE LINK: |
| | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| | 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| | |
| | ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO |
| | SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED |
| | SHEETS FOR COMPARATIVE REVIEW. |
| | |
| | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| | 561-805-6717 OR [email protected] |
| | |