Plan Review Notes
Plan Review Notes For Permit 14060869
Permit Number 14060869
Review Stop M
Sequence Number 1
Notes
Date Text
2014-07-08 18:49:182010 FBC
  
 DENIED BY MECHANICAL
  
 1) SUBMIT TWO COPIES OF EQUIPMENT SIZING CALCULATIONS
 FOR THE HEATING AND COOLING EQUIPMENT. FBCR M1401.3
  
 2) SPECIFY THE SIZE OF ALL DUCTS, GRILL SIZES AND CFMS
 AT EACH SUPPLY OUTLET ON THE PLANS.
  
 3) RETURN AIR CAN NOT BE TAKEN FROM A CLOSET. SHOW HOW
 THE RETURN AIR TO THE AIR HANDLER WILL BE PROVIDED.
 FBCR M 1602.2
  
 4) SHOW COMPLIANCE WITH FBCR M 1602.4 FOR BALANCED
 RETURN AIR.
  