| Plan Review Notes For Permit 14060869 |
| Permit Number |
14060869 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-07-09 14:15:51 | 2010 FBC / 2008 NEC | | | | | | DENIED BY ELECTRIC | | | | | | 1) ACCORDING TO THE ZONING REVIEW THIS LOT IS ZONED AS | | | SINGLE FAMILY AND ONLY ONE METER IS ALLOWED FOR A | | | SINGLE FAMILY DWELLING. SUBMIT AN ELECTRICAL RISER PLAN | | | THAT SHOWS COMPLIANCE WITH THE ZONING CODE AND THE 2008 | | | NEC. | | | | | | 2) THIS ACCESSORY STRUCTURE IS NOT ALLOWED TO HAVE A | | | KITCHEN PER THE ZONING REVIEW. REMOVE THE KITCHEN FROM | | | THE PLANS. | | | | | | 3) SHOW COMPLIANCE WITH NEC 210.52 FOR RECEPTACLE | | | SPACING. | | | | | | 4) SHOW COMPLIANCE WITH NEC 210.12 FOR ARC-FAULT | | | PROTECTION. | | | | | | 5) SHOW COMPLIANCE WITH NEC 406.11 FOR TAMPER-RESISTANT | | | RECEPTACLES. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|