| Plan Review Notes For Permit 14060856 |
| Permit Number |
14060856 |
|
| Review Stop |
Z |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-08-19 13:49:43 | FAILED | | | | | | PROVIDE WRITTEN RESPONSE TO COMMENTS. SEE CLOUDED AREAS | | | ON THE DIGITAL COVER SHEET. | | | | | | 1) PLEASE EXPLAIN HOW THE BUILDING AREA WENT FROM | | | 59,727 SQ. FT. ON REVISION PERMIT NO. 14060173 (ADDED | | | FIRE SEPARATIONS) TO 58,517 SQ. FT. ON THIS REVISION. | | | THE BUILDING PLANS DO NOT SHOW A SMALLER BUILDING. | | | | | | 2) WHY IS THE TOTAL BUILDING AREA OF 58,517 SQ. FT YET | | | THE OCCUPANT LOAD CALCULATION SHOWS 58,690 SQ. FT. | | | | | | 3) WHAT HAPPENED TO THE SQUARE FOOTAGE TABULATION FOR | | | THE LANDLORDS ROOMS? | | | | | | 4) PLEASE REMEMBER THAT ALL THE ROOFTOP MECHANICAL | | | EQUIPMENT NEEDS TO BE SCREENED. | | | | | | 5) THE AWNINGS REQUIRE SEPARATE PERMITS, WITH PLANS, | | | AND THEY SHALL BE CENTERED OVER THEIR RESPECTIVE DOORS. | | | | | | CONTACT ERIC SCHNEIDER @ (561) 822-1446. | | | | | | | | 2014-07-30 09:45:05 | 7/30/14 |
|