 PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 REVIEW COMMENTS.
  
 SHEET B2 E001A
 PANEL A AND B ARE SHOWN AS MAIN LUG ONLY. INDICATE
 WHERE THE MAIN DISCONNECTS ARE LOCATED FOR THESE PANEL
 BOARDS. NEC 240.21, 408.36
  
 SHEET B2 E001
 PANEL BOARDS SHOWN DO NOT MATCH THE RISER PLAN
 SUBMITTED. NEC 215.5
  
 SHEET B2 E002
 ELECTRIC RISER DOES NOT SEEM TO MATCH PANEL SCHEDULES
 SUBMITTED. NEC 215.5
  
  