Plan Review Notes
Plan Review Notes For Permit 14060854
Permit Number 14060854
Review Stop B
Sequence Number 1
Notes
Date Text
2014-06-24 09:52:41RESIDENTIAL (R2) FLOORING, BUILDING REVIEW COMMENTS.
 CODE: 2010 FBC.
  
 1- PROVIDE TWO COPIES OF CORK SOUND INSULATION TEST
 RESULTS SHOWING COMPLIANCE WITH ASTM E 84 OR UL 723 FOR
 THE FLAME SPREAD INDEX AND AND SMOKE -DEVELOPED INDEX
 AS REQUIRED BY SEC. 719.1 OF 2010 FBC.
  
 2- PROVIDE TWO COPIES OF CORK SOUND INSULATION TEST
 RESULTS SHOWING COMPLIANCE WITH ASTM E 90 FOR THE SOUND
 TRANSMISSION CLASS AS REQUIRED BY SEC. 1207.2 OF 2010
 FBC.
  
 3- PROVIDE TWO COPIES OF CORK SOUND INSULATION TEST
 RESULTS SHOWING COMPLIANCE WITH ASTM E 492 FOR THE
 IMPACT INSULATION CLASS AS REQUIRED BY SEC. 1207.3 OF
 2010 FBC.
  
 4- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW. VALUATION TO INCLUDE ALL LABOR, MATERIALS AND
 CONTRACTOR'S OVERHEAD AND PROFIT AS REQUIRED BY SEC.
 109.3 CITY AMENDMENTS TO FBC. PLEASE UPDATE VALUATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712