| Plan Review Notes For Permit 14060851 |
| Permit Number |
14060851 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-06-25 15:16:18 | DATE: 6/25/2014 | | | PROJECT: ANTIQUE ROW | | | PERMIT#: 14060851 | | | CODE: 2008 EDITION OF THE NEC | | | 2010 EDITION OF THE FBC | | | 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, | | | ADMINISTRATION, 2012 FBC SUPPLEMENTS. | | | | | | 1ST ELECTRICAL PLAN REVIEW | | | ACTION: PROVISO | | | | | | LISTING AND LABELING REQUIRED BY AN APPROVED TESTING | | | LAB. | | | IN JUDGING EQUIPMENT, CONSIDERATION SUCH AS THE | | | FOLLOWING SHALL BE EVALUATED: SUITABILITY OF EQUIPMENT | | | MAY BE EVIDENCED BY LISTING OR LABELING. | | | SUITABILITY FOR INSTALLATION AND USE IN CONFORMITY WITH | | | THE PROVISIONS OF THIS CODE. NEC 110.3(A)(1 THRU 8) | | | LISTED OR LABELED EQUIPMENT SHALL BE INSTALLED AND USED | | | IN ACCORDANCE WITH ANY INSTRUCTIONS INCLUDED IN THE | | | LISTING AND LABELING. NEC 110.3(B) | | | | | | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421. | | | 561-805-6717 OR [email protected] | | | |
|