| 2014-08-06 12:05:24 | PLUMBING PLAN REVIEW |
| | PERMIT: 14060781 |
| | ADD: 1845 PALM BEACH LAKES (WHOLE FOODS) |
| | CONT: TO BE DETERMINED |
| | TEL: (561 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 2ND REVIEW |
| | DATE: WED. AUG. 08/2014 |
| | ACTION: PLUMBING PROVISO |
| | |
| | 1) NOTE TO DATE NO PERMIT HAS BEEN BROUGHT IN FOR THE |
| | SIZING OF THE CONCRETE VAULT TYPE INTERCEPTOR FOR THIS |
| | TENANT SPACE, NOR REVIEWED FOR CODE COMPLIANCE BY THE |
| | BUILDING DEPARTMENT. THE GREASE INTERCEPTOR THAT WAS |
| | SET UNDER THE CIVIL PLANS OF THE PALM BEACH OUTLET MALL |
| | DID NOT HAVE SIZING INFORMATION FOR THE OUT PARCELS AND |
| | MAY OR MAY NOT BE SIZED ADEQUATELY TO MEET THE DEMANDS |
| | FOR THIS USAGE OF THIS TENANT. THIS GREASE INTERCEPTOR |
| | IS A CONCRETE VAULT TYPE INTERCEPTOR AND SHOULD BE |
| | SIZED USING THE 2010 FBC-P (TABLE 1003.5.1 THIS IS A |
| | FLORIDA SPECIFIC AMENDMENT TO THE ICC BASE CODE). MV+A |
| | IS USING THE SIZING METHOD OF "DFU" METHOD OF SIZING |
| | WHICH IS FOR HYDROMECHANICAL TYPE INTERCEPTORS. |
| | |
| | THE CITY FOG INSPECTORS (FATS, OILS & GREASE) MONITOR |
| | ALL GREASE INTERCEPTORS TO VERIFY COMPLIANCE WITH THE |
| | CITY?S MUNI CODE SEC. 90-126. PROHIBITIONS AND |
| | LIMITATIONS OF DISCHARGE.(7) MINERAL OIL IN EXCESS OF |
| | 50 MG/L OR ANIMAL/VEGETABLE FATS, WAX, GREASE, OR OILS |
| | IN EXCESS OF 100 MG/L, WHETHER EMULSIFIED OR NOT; OR |
| | SUBSTANCES WHICH MAY SOLIDIFY OR BECOME VISCOUS AT |
| | TEMPERATURES LOWER THAN OR EQUAL TO 150 DEGREES |
| | FAHRENHEIT (65.56 DEGREES CELSIUS). |
| | |
| | IF THIS AMOUNT OF FATS, OILS OR GREASE IS EXCEEDED THE |
| | REQUIRED MAINTENANCE & PUMP-OUT SCHEDULE WILL BE |
| | INCREASED TO KEEP IN COMPLIANCE WITH THE CITY'S |
| | MUNICIPAL CODE OF ORDINANCES. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |