| 2014-06-30 15:22:41 | PLUMBING PLAN REVIEW |
| | PERMIT: 14060781 |
| | ADD: 1845 PALM BCH LAKES BLVD BLDG "C" WHOLE FOODS |
| | CONT: TBD |
| | TEL: (561 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: MON. JUNE 30/ 2014 |
| | ACTION: DENIED |
| | |
| | 1) A SEPARATE PERMIT IS REQUIRED FOR GREASE |
| | INTERCEPTORS. SHEET P101 INDICATES THERE IS A EXISTING |
| | 4 INCH EXISTING GREASY BUILDING DRAIN. NOTE TO DATE |
| | THERE HAS BEEN NO GREASE INTERCEPTOR APPLIED FOR OR |
| | REVIEWED BY THIS DEPARTMENT. THERE IS APPARENTLY GREASE |
| | INTERCEPTORS THAT WERE REVIEWED BY THE ENGINEERING |
| | DEPARTMENT BUT NOT BY THE BUILDING DEPARTMENT. ALL |
| | GREASE INTERCEPTORS ARE TO COMPLY WITH THE 2010 |
| | FBC-PLUMBING , IF THIS IS A CONCRETE VAULT TYPE OF |
| | GREASE INTERCEPTORS THEY ARE TO BE DESIGNED TO FBC- |
| | PLUMBING TABLE 1003.5.1. |
| | |
| | 2) A SEPARATE PERMIT WILL ALSO NEED TO BE OBTAINED FOR |
| | A FUEL GAS PERMIT. SHEET P301 SHOWS THE GAS ISOMETRIC. |
| | THESE ARE THE REQUIREMENTS TO OBTAIN A FUEL GAS PERMIT: |
| | |
| | 2.1. SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS ALL |
| | CUT SECTIONS OF PIPE, DIAMETER AND CORRESPONDING |
| | LENGTHS PER FBC-2010 FUEL GAS. |
| | |
| | 2.2. SHOW TYPE OF PIPING MATERIAL BEING INSTALLED, ALL |
| | PIPE SIZES, AND THE EDH NUMBER OF CORRUGATED STAINLESS |
| | STEEL TUBING FOR EACH PIPE SIZE IF BEING USED. |
| | |
| | 2.3. TYPE OF GAS, (LP OR NATURAL). |
| | |
| | 2.4. BTU LOAD OF EACH APPLIANCE AND THE TOTAL BTU LOAD |
| | ON THE SYSTEM. REFER TO THE FBC-2010 FUEL GAS SECS. |
| | 401.8 THRU 402.6.1 AND TABLES 402.4(1) THRU 402.4(35) |
| | |
| | 2.5. SHOW THE DISTANCE FROM THE POINT OF DELIVERY, |
| | (METER), TO THE MOST REMOTE OUTLET IN THE BUILDING |
| | AND/OR SYSTEM PER THE FBC-2010 FUEL GAS APPENDIX A ? |
| | USE OF CAPACITY SECTION A.3.1(4) |
| | |
| | 2.6. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE |
| | FBC-2010 FUEL GAS CODE SEC. 304 |
| | |
| | 2.7. INDICATE THE DELIVERY PRESSURE (PSI) PER FBC-2010 |
| | FUEL GAS SEC. 402.2. IF NATURAL GAS SPECIFY .5 PSI OR 2 |
| | PSI. |
| | |
| | 2.8. SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE |
| | AND TERMINATION OF THE GAS VENTS PER FBC-2010 FUEL GAS |
| | CODE SEC. 502 THRU 505. |
| | |
| | 2.9. SUBMIT MANUFACTURE SHEETS FOR ALL GAS EQUIPMENT TO |
| | VERIFY COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND |
| | FBC-2010 FUEL GAS SEC. 402.2 |
| | |
| | 3) PLEASE PROVIDE ADDITIONAL INFORMATION 107.2.1.3. |
| | SHEET A101 IN (2) OF THE REFRIGARATED ROOMS THERE IS |
| | EQUIPMENT IDENTIFIED AS EQ. 801 GRINDER THIS EQUIPMENT |
| | DOES NOT SHOW UP ON P101 NOR P401, IS A DETAIL ON P402 |
| | IF THIS IS PART OF THE PLUMBING SYSTEM, THAT SHOULD GO |
| | TO THE GREASY WASTE NOT LOCATED ON PLANS, THEY WILL |
| | NEED TO COMPLY WITH 2010 FBC-P 1003.3.2 PROVIDE THE |
| | MANUFACTURERS SPECIFICATIONS. . |
| | |
| | 4) NEITHER P101 NOR P102 INDICATE THE AMOUNT OF |
| | DRAINAGE FIXTURE UNITS ON THE HORIZONTAL FIXTURE |
| | BRANCHES (TABLE 710.1(2) NOR THE BUILDING DRAIN FOR THE |
| | SANITARY OR GREASY WASTE TABLE 710.1(1). |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR |
| | YOUR ANTICIPATED COOPERATION. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |