Plan Review Notes
Plan Review Notes For Permit 14060781
Permit Number 14060781
Review Stop P
Sequence Number 1
Notes
Date Text
2014-06-30 15:22:41PLUMBING PLAN REVIEW
 PERMIT: 14060781
 ADD: 1845 PALM BCH LAKES BLVD BLDG "C" WHOLE FOODS
 CONT: TBD
 TEL: (561
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. JUNE 30/ 2014
 ACTION: DENIED
  
 1) A SEPARATE PERMIT IS REQUIRED FOR GREASE
 INTERCEPTORS. SHEET P101 INDICATES THERE IS A EXISTING
 4 INCH EXISTING GREASY BUILDING DRAIN. NOTE TO DATE
 THERE HAS BEEN NO GREASE INTERCEPTOR APPLIED FOR OR
 REVIEWED BY THIS DEPARTMENT. THERE IS APPARENTLY GREASE
 INTERCEPTORS THAT WERE REVIEWED BY THE ENGINEERING
 DEPARTMENT BUT NOT BY THE BUILDING DEPARTMENT. ALL
 GREASE INTERCEPTORS ARE TO COMPLY WITH THE 2010
 FBC-PLUMBING , IF THIS IS A CONCRETE VAULT TYPE OF
 GREASE INTERCEPTORS THEY ARE TO BE DESIGNED TO FBC-
 PLUMBING TABLE 1003.5.1.
  
 2) A SEPARATE PERMIT WILL ALSO NEED TO BE OBTAINED FOR
 A FUEL GAS PERMIT. SHEET P301 SHOWS THE GAS ISOMETRIC.
 THESE ARE THE REQUIREMENTS TO OBTAIN A FUEL GAS PERMIT:
  
 2.1. SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS ALL
 CUT SECTIONS OF PIPE, DIAMETER AND CORRESPONDING
 LENGTHS PER FBC-2010 FUEL GAS.
  
 2.2. SHOW TYPE OF PIPING MATERIAL BEING INSTALLED, ALL
 PIPE SIZES, AND THE EDH NUMBER OF CORRUGATED STAINLESS
 STEEL TUBING FOR EACH PIPE SIZE IF BEING USED.
  
 2.3. TYPE OF GAS, (LP OR NATURAL).
  
 2.4. BTU LOAD OF EACH APPLIANCE AND THE TOTAL BTU LOAD
 ON THE SYSTEM. REFER TO THE FBC-2010 FUEL GAS SECS.
 401.8 THRU 402.6.1 AND TABLES 402.4(1) THRU 402.4(35)
  
 2.5. SHOW THE DISTANCE FROM THE POINT OF DELIVERY,
 (METER), TO THE MOST REMOTE OUTLET IN THE BUILDING
 AND/OR SYSTEM PER THE FBC-2010 FUEL GAS APPENDIX A ?
 USE OF CAPACITY SECTION A.3.1(4)
  
 2.6. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE
 FBC-2010 FUEL GAS CODE SEC. 304
  
 2.7. INDICATE THE DELIVERY PRESSURE (PSI) PER FBC-2010
 FUEL GAS SEC. 402.2. IF NATURAL GAS SPECIFY .5 PSI OR 2
 PSI.
  
 2.8. SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE
 AND TERMINATION OF THE GAS VENTS PER FBC-2010 FUEL GAS
 CODE SEC. 502 THRU 505.
  
 2.9. SUBMIT MANUFACTURE SHEETS FOR ALL GAS EQUIPMENT TO
 VERIFY COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND
 FBC-2010 FUEL GAS SEC. 402.2
  
 3) PLEASE PROVIDE ADDITIONAL INFORMATION 107.2.1.3.
 SHEET A101 IN (2) OF THE REFRIGARATED ROOMS THERE IS
 EQUIPMENT IDENTIFIED AS EQ. 801 GRINDER THIS EQUIPMENT
 DOES NOT SHOW UP ON P101 NOR P401, IS A DETAIL ON P402
 IF THIS IS PART OF THE PLUMBING SYSTEM, THAT SHOULD GO
 TO THE GREASY WASTE NOT LOCATED ON PLANS, THEY WILL
 NEED TO COMPLY WITH 2010 FBC-P 1003.3.2 PROVIDE THE
 MANUFACTURERS SPECIFICATIONS. .
  
 4) NEITHER P101 NOR P102 INDICATE THE AMOUNT OF
 DRAINAGE FIXTURE UNITS ON THE HORIZONTAL FIXTURE
 BRANCHES (TABLE 710.1(2) NOR THE BUILDING DRAIN FOR THE
 SANITARY OR GREASY WASTE TABLE 710.1(1).
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  