2014-07-21 13:20:46PLAN DENIED
 1) SEPARATE PLANS, APPLICATION AND PERMIT REQUIRED FOR
 HOOD AND REFRIGATION. PER SECTION 107 FBC 2010
 2) PROVIDE ENGINEER DETAIL ON THE HOOD EXHAUST FAN AND
 SUPPLY FANS, CURB TIE DOWN TO THE ROOF AND FAN TIE DOWN
 TO CURB. PROVIDE SPACING ON THE ANCHOR PROVIDE TYPE
 AND SIZE OF ANCHOR USED. ON HOOD PLANS. PER SECTION
 301.12 WIND RESISTANCE 2010 FBC (M)
 3) PROVIDE AN ENGINEER DETAIL ON REFRIGATION CONDENSER
 STAND
 TIE DOWN TO ROOF AND CONDENSER TIE DOWN TO STAND. PER
 SECTION
 301.12 WIND RESISTANCE 2010 FBC (M).
  
 PLAN REVIEW BY HAROLD MOSER