| Plan Review Notes For Permit 14060781 |
| Permit Number |
14060781 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-07-21 13:20:46 | PLAN DENIED | | | 1) SEPARATE PLANS, APPLICATION AND PERMIT REQUIRED FOR | | | HOOD AND REFRIGATION. PER SECTION 107 FBC 2010 | | | 2) PROVIDE ENGINEER DETAIL ON THE HOOD EXHAUST FAN AND | | | SUPPLY FANS, CURB TIE DOWN TO THE ROOF AND FAN TIE DOWN | | | TO CURB. PROVIDE SPACING ON THE ANCHOR PROVIDE TYPE | | | AND SIZE OF ANCHOR USED. ON HOOD PLANS. PER SECTION | | | 301.12 WIND RESISTANCE 2010 FBC (M) | | | 3) PROVIDE AN ENGINEER DETAIL ON REFRIGATION CONDENSER | | | STAND | | | TIE DOWN TO ROOF AND CONDENSER TIE DOWN TO STAND. PER | | | SECTION | | | 301.12 WIND RESISTANCE 2010 FBC (M). | | | | | | PLAN REVIEW BY HAROLD MOSER | | | [email protected] | | | OFFICE 561-805-6732 | | | FAX 561-805-6676 |
|