| 2014-07-25 08:15:42 | FUEL GAS PLAN REVIEW |
| | PERMIT: 14060781 |
| | ADD: 1845 PALM BCH LAKES BLVD BLDG "C" WHOLE FOODS |
| | CONT: TBD |
| | TEL: (561 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2ND REVIEW 1ST REVIEW WAS PART OF THE PLUMBING REVIEW |
| | DATE: FRI. JULY 25/ 2014 |
| | |
| | ACTION: PROVISO |
| | FUEL GAS APPROVED WITH EXCEPTION! |
| | |
| | THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO |
| | CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO |
| | INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE |
| | ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE |
| | ADDITIONAL REVIEWS WITH ASSOCIATED FEES. |
| | |
| | NOTE: A SEPARATE PERMIT WILL ALSO NEED TO BE OBTAINED |
| | FOR A FUEL GAS PERMIT. SHEET P301 SHOWS THE GAS |
| | ISOMETRIC. THESE ARE THE REQUIREMENTS TO OBTAIN A FUEL |
| | GAS PERMIT: |
| | |
| | 1) WITHOUT THE SUBMITTAL OF THE MANUFACTURERS |
| | SPECIFICATION SHEETS FOR THE GAS EQUIPMENT TO BE |
| | INSTALLED SIZING CAN NOT BE VARIFIED, CONTRACTOR IS AT |
| | OWN RISK. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA 54, |
| | NFPA 58, AND FBC-2010 FUEL GAS SEC. 402.2. THE |
| | MANUFACTURER'S SPECIFICATIONS CAN BE SUBMITTED AS A |
| | DEFERRAL BUT AT RISK. |
| | |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |