| 2014-06-30 13:52:47 | BUILDING PLAN REVIEW |
| | PERMIT: 14060781 |
| | ADD: 1845 PALM BCH LAKES BLVD BLDG "C" WHOLE FOODS |
| | CONT: TBD |
| | TEL: (561 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: MON. JUNE 30/ 2014 |
| | ACTION: DENIED |
| | |
| | 1) SHEET CS-2 INDICATES UNDER THE CODE ANALYSIS |
| | EXISTING BUILDING. NOTE THIS IS A SHELL BUILDING, NO |
| | FIRST TENANCY, THE 2010 FBC-BUILDING WILL BE USED FOR |
| | NEW BUILDINGS SINCE THERE HAS NEVER BEEN A C. O. |
| | ISSUED. |
| | |
| | 2) SHEET CS-2 INDICATES A MEZZANINE AREA D-3 TO BE USED |
| | SOLEY FOR REFRIGARANT / WATER HEATING, NO STORAGE. THE |
| | UPPER HALF OF THE STAIRWAY IS ENCLOSED WITH A DOOR. THE |
| | 2010 FBC-B 505.4 DOES ALLOW FOR ENCLOSED MEZZANINES |
| | WITH AN OCCUPANT LOAD OF LESS THAN 10 WHICH THIS DOES. |
| | THE ENCLOSING THE UPPER HALF OF THE STAIR DOES NOT GIVE |
| | A WORK MAN IN THIS SPACE ANY NOTIFICATION OF A FIRE AND |
| | SMOKE AND THE AMOUNT OF NOISE THE REFRIGARATION |
| | EQUIPMENT. FOR THIS REASON WE WOULD LIKE TO SUGGEST A |
| | STROBE THAT WOULD TIE INTO THE ALARM SYSTEM TO ALERT |
| | ANY WORKMAN IN THIS LIMITED SPACE TO EVACUATE. THIS |
| | SPACE NOW DOES NOT COMMUNICATE WITH THE REMAINDER OF |
| | THE 1 ST FLOOR. THERE IS NO ACTUAL CODE SECTION TO |
| | ADDRESS OUR CONCERNS, THIS CAN ONLY BE A SUGGESTION. |
| | |
| | 3) SHEET A2.07 IDENTIFIES THE DOORS WITHIN TTHE |
| | TENANCY. DOORS 100,& 101 ARE IDENTIFIED AS EXISTING THE |
| | DOOR SCHEDULE FOUND ON A702 |
| | THE NOTES DO NOT PROVIDE THE TYPE OF HARDWARE, NOTES |
| | INDICATE CYLINDER LOCK TO BE INSTALLED. PLEASE SHOW |
| | COMPLIANCE WITH 2010 FBC-B |
| | 008.1.9.3 LOCKS AND LATCHES. 2.2. A READILY VISIBLE |
| | DURABLE SIGN IS POSTED ON THE EGRESS SIDE ON OR |
| | ADJACENT TO THE DOOR STATING: THIS DOOR TO REMAIN |
| | UNLOCKED WHEN BUILDING IS OCCUPIED. THE SIGN SHALL BE |
| | IN LETTERS 1 INCH (25 MM) HIGH ON A CONTRASTING |
| | BACKGROUND. |
| | |
| | 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE & REPLACE ANY PAGES AS NECESSARY. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |