| 2014-07-03 14:51:39 | 2010 FBC |
| | |
| | DENIED BY BUILDING |
| | |
| | 1) THERE IS ANOTHER PERMIT ( #14060659) THAT HAS BEEN |
| | APPLIED FOR A TRASH ENCLOSURE AT THIS ADDRESS. IS THIS |
| | THE SAME ONE THAT IS #3 ON THE LIST OF WORK THAT WAS |
| | SUBMITTED? PLEASE CLARIFY. CITY AMENDMENTS 107.2.1 |
| | |
| | 2) SUBMIT TWO SETS OF PLANS AND STRUCTURAL DETAILS FOR |
| | THE EXTERIOR ENCLOSED EGRESS STAIRS THAT ARE BEING |
| | REPLACED. FBCR 311.7 |
| | |
| | 3) THE NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR |
| | THE DESIGN IS REQUIRED ON THE DRAWINGS. CITY AMENDMENTS |
| | 107.2.1 |
| | |
| | 4) SUBMIT TWO SETS OF FLOOR PLANS FOR THE FIRST AND |
| | SECOND FLOORS WITH THE ROOM TYPES LABELED AND THE |
| | WINDOW TYPES AND SIZES SPECIFIED ON THE PLANS. IF ANY |
| | OF THE OPENINGS HAVE MULTIPLE WINDOW TYPES JOINED |
| | TOGETHER WITH STRUCTURAL MULLIONS SPECIFY THE TYPE AND |
| | SIZE OF EACH WINDOW AND THE MULL LENGTH AND ORIENTATION |
| | ( PROVIDE AN ELEVATION OF THE WINDOWS IF NECESSARY FOR |
| | CLARITY). CITY AMENDMENTS 107.2.1 & FBCR 301.2.1 |
| | |
| | 5) THE PRODUCT APPROVAL ( NOA NO. 11-1013.19) THAT WAS |
| | SUBMITTED FOR THE LARGE MISSILE IMPACT RATED SINGLE |
| | HUNG PGT WINDOWS IS EXPIRED. SUBMIT TWO COPIES OF |
| | CURRENT PRODUCT APPROVALS FOR THE WINDOWS. DCA RULE |
| | 9N-3 |
| | |
| | 6) SHOW COMPLIANCE WITH FBCR 314.3.1 FOR REQUIRED SMOKE |
| | ALARMS. |
| | |
| | 7) IN ORDER TO SPEED PLAN REVIEW TIME, PLEASE SUBMIT A |
| | RESPONSE LETTER INDICATING HOW EACH OF THE REVIEW |
| | COMMENTS HAS BEEN ADDRESSED. |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)805-6714 |