2014-07-15 09:47:46DATE: 7/14/2014
 PROJECT: BELLMART SHOPPES LEASE SPACE 640
 PERMIT#: 14060569
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 2ND ELECTRICAL PLAN REVIEW
 ACTION: PROVISO
  
 1) WIRING IN PATIENT CARE AREAS SHALL COMPLY WITH NEC
 517.13(A) AND (B).
  
 2) ELECTRIC DRINKING FOUNTAINS SHALL BE PROTECTED WITH
 GROUND-FAULT CIRCUIT-INTERRUPTER PROTECTION. NEC 422.52
  
 3) ALL EMERGENCY LIGHTING SHALL BE CONNECTED TO A
 LIGHTING CIRCUIT WITHIN THE AREA THEY OCCUPY. NEC
 700.12(F)
  
 4) UNLESS SPECIFICALLY PERMITTED IN FLEXIBLE CORDS
 SHALL NOT BE USED FOR THE FOLLOWING: WHERE CONCEALED BY
 WALLS, FLOORS, OR CEILINGS OR LOCATED ABOVE SUSPENDED
 OR DROPPED CEILINGS NEC 400.7,
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]