| 2014-07-15 09:47:46 | DATE: 7/14/2014 | | | PROJECT: BELLMART SHOPPES LEASE SPACE 640 | | | PERMIT#: 14060569 | | | CODE: 2008 EDITION OF THE NEC | | | 2010 EDITION OF THE FBC | | | 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, | | | ADMINISTRATION, 2012 FBC SUPPLEMENTS. | | | | | | 2ND ELECTRICAL PLAN REVIEW | | | ACTION: PROVISO | | | | | | 1) WIRING IN PATIENT CARE AREAS SHALL COMPLY WITH NEC | | | 517.13(A) AND (B). | | | | | | 2) ELECTRIC DRINKING FOUNTAINS SHALL BE PROTECTED WITH | | | GROUND-FAULT CIRCUIT-INTERRUPTER PROTECTION. NEC 422.52 | | | | | | 3) ALL EMERGENCY LIGHTING SHALL BE CONNECTED TO A | | | LIGHTING CIRCUIT WITHIN THE AREA THEY OCCUPY. NEC | | | 700.12(F) | | | | | | 4) UNLESS SPECIFICALLY PERMITTED IN FLEXIBLE CORDS | | | SHALL NOT BE USED FOR THE FOLLOWING: WHERE CONCEALED BY | | | WALLS, FLOORS, OR CEILINGS OR LOCATED ABOVE SUSPENDED | | | OR DROPPED CEILINGS NEC 400.7, | | | | | | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, | | | 561-805-6717 OR [email protected] |
|