| 2014-07-03 07:45:11 | PLUMBING PLAN REVIEW |
| | PERMIT:14060569 |
| | ADD: 500 BELVEDERE DR SUITE # 640 |
| | CONT: ALL PURPOSE CONSTRUCTION |
| | TEL: (561)718-7578 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: THURS. JULY 03/ 2014 |
| | ACTION: DENIED |
| | |
| | 1) ALL THREE TOLIET ROOMS ARE INDICATED TO HAVE ALL NEW |
| | WALLS, PLEASE REVIEW THE 2010 FL ACCESIBILITY CODE IN |
| | REGUARDS TO |
| | 604.3.1 SIZE. |
| | CLEARANCE AROUND A WATER CLOSET SHALL BE 60 INCHES |
| | (1525 MM) MINIMUM MEASURED PERPENDICULAR FROM THE SIDE |
| | WALL AND 56 INCHES (1420 MM) MINIMUM MEASURED |
| | PERPENDICULAR FROM THE REAR WALL. |
| | 604.3.2 OVERLAP. |
| | THE REQUIRED CLEARANCE AROUND THE WATER CLOSET SHALL BE |
| | PERMITTED TO OVERLAP THE WATER CLOSET, ASSOCIATED GRAB |
| | BARS, DISPENSERS, SANITARY NAPKIN DISPOSAL UNITS, COAT |
| | HOOKS, SHELVES, ACCESSIBLE ROUTES, CLEAR FLOOR SPACE |
| | AND CLEARANCES REQUIRED AT OTHER FIXTURES, AND THE |
| | TURNING SPACE. NO OTHER FIXTURES OR OBSTRUCTIONS SHALL |
| | BE LOCATED WITHIN THE REQUIRED WATER CLOSET CLEARANCE. |
| | |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |