| 2014-07-03 07:42:35 | BUILDING PLAN REVIEW |
| | PERMIT:14060569 |
| | ADD: 500 BELVEDERE DR SUITE # 640 |
| | CONT: ALL PURPOSE CONSTRUCTION |
| | TEL: (561)718-7578 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: THURS. JULY 03/ 2014 |
| | ACTION: DENIED |
| | |
| | 1) THE HALL WAY BETWEEN THE COUNSELING OFFICE AND THE |
| | DOCTORS OFFICE THE PLANS INDICATE A HALL WAY WIDTH OF |
| | 3'-8" WIDE. THERE IS A 6 INCH OFFSET IN THE CORRIDOR |
| | WALL INCREASING THE WIDTH TO 4'-2" WHERE TOLIET ROOMS |
| | ARE LOCATED. WHEN MEASURING THE ROOM WITH A SCALE THEY |
| | MEASURE 6'-6", PLEASE REVIEW SHEET A2 THIS DETAIL |
| | MEASURES A 7'-0" INTERIOR MEASUREMENT. DISCREPANCY IN |
| | PLANS.107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED. |
| | |
| | 2) ALL THREE TOLIET ROOMS ARE INDICATED TO HAVE ALL NEW |
| | WALLS, PLEASE REVIEW THE 2010 FL ACCESIBILITY CODE IN |
| | REGUARDS TO |
| | 604.3.1 SIZE. |
| | CLEARANCE AROUND A WATER CLOSET SHALL BE 60 INCHES |
| | (1525 MM) MINIMUM MEASURED PERPENDICULAR FROM THE SIDE |
| | WALL AND 56 INCHES (1420 MM) MINIMUM MEASURED |
| | PERPENDICULAR FROM THE REAR WALL. |
| | 604.3.2 OVERLAP. |
| | THE REQUIRED CLEARANCE AROUND THE WATER CLOSET SHALL BE |
| | PERMITTED TO OVERLAP THE WATER CLOSET, ASSOCIATED GRAB |
| | BARS, DISPENSERS, SANITARY NAPKIN DISPOSAL UNITS, COAT |
| | HOOKS, SHELVES, ACCESSIBLE ROUTES, CLEAR FLOOR SPACE |
| | AND CLEARANCES REQUIRED AT OTHER FIXTURES, AND THE |
| | TURNING SPACE. NO OTHER FIXTURES OR OBSTRUCTIONS SHALL |
| | BE LOCATED WITHIN THE REQUIRED WATER CLOSET CLEARANCE. |
| | |
| | 3) THE WIDTH OF THE CORRIDOR AND DOOR SWING IS ALSO A |
| | CONCERN, THE NEED TO COMPLY WITH FBC-B 008.1.9.11 |
| | DURING ITS SWING, ANY DOOR IN A MEANS OF EGRESS SHALL |
| | LEAVE UNOBSTRUCTED AT LEAST ONE HALF OF THE REQUIRED |
| | WIDTH OF AN AISLE, CORRIDOR, PASSAGEWAY, OR LANDING, |
| | NOR PROJECT MORE THAN 7 INCHES (178 MM) INTO THE |
| | REQUIRED WIDTH OF AN AISLE, CORRIDOR, PASSAGEWAY OR |
| | LANDING, WHEN FULLY OPEN. |
| | THE MINIMUM CORRIDOR WIDTH FOR THIS OCCUPANT LOAD WOULD |
| | BE 36+18= 54 INCHES. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR |
| | YOUR ANTICIPATED COOPERATION. |
| | |