| Plan Review Notes For Permit 14060547 |
| Permit Number |
14060547 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-06-16 15:26:19 | DATE: 6/16/2014 | | | PROJECT: GAINES PARK BASKETBALL REPLACEMENT | | | PERMIT#: 14060547 | | | CODE: 2008 EDITION OF THE NEC | | | 2010 EDITION OF THE FBC | | | 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, | | | ADMINISTRATION, 2012 FBC SUPPLEMENTS. | | | | | | ELECTRICAL PLAN REVIEW | | | | | | 1ST REVIEW | | | ACTION: DENIED | | | | | | 1) EACH MULTI-WIRE BANCH CIRCUIT SHALL BE PROVIDED WITH | | | A MEANS THAT WILL SIMULTANTOIUSLY DISCONNECT ALL | | | UNGROUNDED CONDUCTORS AT THE POINT WHERE THE BRANCH | | | CIRCUIT ORIGINATES. 210.4 (B) INDICATE IF THE DEDICATED | | | CIRCUIT ALSO IMPLIES A DEDICATED NEUTRAL. | | | | | | 2) INDICATE THE LOCATION AND WIRINF MEATHOD FOR THE | | | ELEVATION KEY SWITCH. THE MANUFACTURER NOTES CALL FOR A | | | KEY SWITCH FOR OPERATION OF THE ELEVATION OF THE GOAL. | | | THE ELECTRICAL PLANS DO NOT INDICATE THE LOCATION OR | | | WIRING MEATHOD FOR THE KEY SWITCH. | | | | | | 3) ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND | | | ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF | | | THE PERSON RESPONSIBLE FOR THE DESIGN. FBC 107.2.1. | | | KNIGHT ELECTRIC IS NOT THE PERSON RESPONSIBLE FOR THE | | | DESIGN. | | | | | | DAVID HAYES, ELECTRICAL PLANS EXAMINER. PX3421, | | | 561-805-6717, [email protected] | | | | | | |
|