2014-06-17 07:21:411ST REVIEW:
  
 THE DOOR/WINDOW REPLACEMENT ASPECT OF THIS PROJECT IS
 REQUIRED TO BE EVALUATED BY A DESIGN PROFESSIONAL.
 PLEASE PROVIDE AN ENGINEERED WIND DESIGN WHICH
 CONSIDERS BUILDING HEIGHT, WIND SPEED, WIND EXPOSURE,
 AND LOCATION OF THE OPENINGS. THE PROPOSED INSTALLATION
 MUST MEET THE RESULTING DESIGN PRESSURES.
  
 FBC107.1 GENERAL. SUBMITTAL DOCUMENTS CONSISTING OF
 CONSTRUCTION DOCUMENTS, THE CONSTRUCTION DOCUMENTS
 SHALL BE PREPARED BY A REGISTERED DESIGN PROFESSIONAL
 WHERE REQUIRED BY CHAPTER 471, FLORIDA STATUTES& 61G15
 FLORIDA ADMINISTRATIVE CODE OR CHAPTER 481, FLORIDA
 STATUTES& 61G1 FLORIDA ADMINISTRATIVE CODE.
  
 FBC 107.3.5.1.1(8) - PROVIDE WIND DESIGN LOADS/DESIGN
 PRESSURES PURSUANT TO FBC-CHAPTER 16
  