| Plan Review Notes For Permit 14060537 |
| Permit Number |
14060537 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-07-11 18:32:00 | 2010 FBC | | | | | | DENIED BY BUILDING | | | | | | 1) THE ENERGY CALCULATION FORM IS REQUIRED TO BE SIGNED | | | BY THE OWNER/AGENT. FBC ENERGY CONSERVATION SECTION | | | 103.2.3.2 | | | | | | 2) THE PRODUCT APPROVALS ARE REQUIRED TO BE REVIEWED | | | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD FOR | | | THE PROJECT. CITY AMENDMENTS 107.2.1 | | | | | | 3) SUBMIT TWO COPIES OF THE PRODUCT APPROVALS FOR THE | | | ROOFING MATERIAL AS REQUIRED BY DCA RULE 9N-3. | | | | | | NOTE: A SEPARATE PERMIT, APPLICATION AND REVIEW IS | | | REQUIRED FOR THE NEW PAVER WALKWAY AND THE FENCE. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|