2014-06-16 16:38:45****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. THE MOISTURE SURVEY INDICATES HIGH MOISTURE IN A
 PORTION OF THE ROOF. SEE FBC 1510.3, IT IS NOT CLEAR
 HOW THE CONTRACTOR PROPOSES TO DEAL WITH THIS ISSUE.
 ENGINEER HAS SPECIFICALLY STATED IN THE MOISTURE SURVEY
 THAT AREA C3 EXCEEDS THE ACCEPTABLE AMOUNT OF MOISTURE
 ALLOWED, APPROXIMATELY 11.25% OF THE ROOF.
  