Date Text
2014-07-08 17:46:562010 FBC
  
 DENIED BY BUILDING
  
 1) THE ENGINEERING IN YOUR EMAIL REQUIRES THE POSITIVE
 AND NEGATIVE PRESSURES SPECIFIC TO THE SITE TO BE
 DETERMINED BY OTHERS. SEE GENERAL NOTE 2 AND THE
 ALLOWABLE DESIGN PRESSURE NOTES IN THE UPPER RIGHT HAND
 CORNER. THIS STRUCTURE IS LOCATED IN A 170 MPH VULT
 WIND SPEED AND THE EXPOSURE CATEGORY IS C. THE
 ALLOWABLE PRESSURE FOR THE 20 KW GENERATOR PAD FROM THE
 ENGINEERING IS 35.39 PSF. THIS WILL NOT MEET THE
 REQUIRED WIND LOAD PRESSURES. FS 471.025 AND FAC
 61G15-23.002 REQUIRE ORIGINAL SIGNED AND SEALED
 DOCUMENTS WHEN SUBMITTED FOR PUBLIC RECORD.
 THE ENGINEERING THAT WAS ORIGINALLY SUBMITTED WOULD BE
 ACCEPTABLE IF IT DID NOT SPECIFY SPECIFIC MODEL NUMBERS
 OR IF THE MODELS 006244-0, 006250-0 FOR THE 20 KW
 GENERATOR PAPER WORK THAT WAS PROVIDED WERE LISTED.
  
 2) SUBMIT TWO COPIES OF INSTALLATION INSTRUCTIONS FOR
 THE GENERATOR. FBCR G2408.1
  
 3) SPECIFY THE LOCATION OF THE GENERATOR IN RELATION TO
 OPENINGS IN THE WALLS AND OVERHANG OF THE DWELLING.
 FBCR G2408.1
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]