2014-08-05 07:41:48DATE: 8/5/2014
 PROJECT: CONSTRUCTION TRAILER
 PERMIT#: 14060484
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 2ND ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) ACCORDING TO THE CONTRACTOR'S RESPONSE LETTER TO THE
 PREVIOUS ELECTRICAL COMMENTS THE PLANS SUBMITTED ON
 PERMIT #14070239 HAVE THE INFORMATION REQUESTED.
 THE LOAD CALCULATION SUBMITTED INDIACTES A LOAD OF 63.4
 AMPS ON PANEL A AND 60.5 AMPS AN PANEL B. I PULLED THE
 PLANS FROM PERMIT #14070239 AND DETERMINED THAT THE
 RISER DIAGRAM ON THAT PERMIT INDICATE A 60AMP FEEDER TO
 EACH PANEL WHICH WOULD BE UNDERSIZED FOR THE LOAD.
 EITHER SUBMIT A REVISION TO PERMIT #14070239 WITH A
 CORRECTED RISER DIAGRAM WITH ADAQUATE AMPACITY TO
 SUPPORT THE LOAD TO BE SERVED OR RE-SUBMIT THIS PERMIT
 APPLICATION WITH A RISER DIAGRAM WITH ADAQUATE AMPACITY
 TO SUPPORT THE LOAD TO BE SERVED.
  
 2) ACCORDING TO THE CONTRACTORS RESPONSE LETTER UNDER
 THE PLUMBING REVIEW COMMENTS DRINKING FOUNTAINS WILL BE
 PROVIDED. THE CUT SHEET SUBMITTED WITH THE RE-SUBMITTAL
 ARE FOR ELECTRICAL DRINKING FOUNTAINS THAT REQUIRE A
 GFI PROTECTED OUTLET. SEE NEC 422.52 ELECTRIC DRINKING
 FOUNTAINS.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]