| 2014-08-05 07:41:48 | DATE: 8/5/2014 |
| | PROJECT: CONSTRUCTION TRAILER |
| | PERMIT#: 14060484 |
| | CODE: 2008 EDITION OF THE NEC |
| | 2010 EDITION OF THE FBC |
| | 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| | ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| | |
| | 2ND ELECTRICAL PLAN REVIEW |
| | ACTION: DENIED |
| | |
| | 1) ACCORDING TO THE CONTRACTOR'S RESPONSE LETTER TO THE |
| | PREVIOUS ELECTRICAL COMMENTS THE PLANS SUBMITTED ON |
| | PERMIT #14070239 HAVE THE INFORMATION REQUESTED. |
| | THE LOAD CALCULATION SUBMITTED INDIACTES A LOAD OF 63.4 |
| | AMPS ON PANEL A AND 60.5 AMPS AN PANEL B. I PULLED THE |
| | PLANS FROM PERMIT #14070239 AND DETERMINED THAT THE |
| | RISER DIAGRAM ON THAT PERMIT INDICATE A 60AMP FEEDER TO |
| | EACH PANEL WHICH WOULD BE UNDERSIZED FOR THE LOAD. |
| | EITHER SUBMIT A REVISION TO PERMIT #14070239 WITH A |
| | CORRECTED RISER DIAGRAM WITH ADAQUATE AMPACITY TO |
| | SUPPORT THE LOAD TO BE SERVED OR RE-SUBMIT THIS PERMIT |
| | APPLICATION WITH A RISER DIAGRAM WITH ADAQUATE AMPACITY |
| | TO SUPPORT THE LOAD TO BE SERVED. |
| | |
| | 2) ACCORDING TO THE CONTRACTORS RESPONSE LETTER UNDER |
| | THE PLUMBING REVIEW COMMENTS DRINKING FOUNTAINS WILL BE |
| | PROVIDED. THE CUT SHEET SUBMITTED WITH THE RE-SUBMITTAL |
| | ARE FOR ELECTRICAL DRINKING FOUNTAINS THAT REQUIRE A |
| | GFI PROTECTED OUTLET. SEE NEC 422.52 ELECTRIC DRINKING |
| | FOUNTAINS. |
| | |
| | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| | 561-805-6717 OR [email protected] |