| Plan Review Notes For Permit 14060484 |
| Permit Number |
14060484 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-07-07 15:03:22 | DATE: 7/7/2014 | | | PROJECT: HILTON HOTEL | | | PERMIT#: 14060484 | | | CODE: 2008 EDITION OF THE NEC | | | 2010 EDITION OF THE FBC | | | 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, | | | ADMINISTRATION, 2012 FBC SUPPLEMENTS. | | | | | | 1ST ELECTRICAL PLAN REVIEW | | | ACTION: DENIED | | | | | | ELECTRICAL PLANS REQUIRED FOR THE FOLLOWING: | | | | | | 1) LOAD CALCULATION TO INDICATE THE TOTAL CONNECTED | | | LOAD AT TRAILER. | | | 2) SITE TO SHOW LOCATION OF TRAILER RELATIVE TO UTILITY | | | SOURCE AND SERVICE EQUIPMENT REQUIRED TO FEED TRAILER. | | | 3) A ONE LINE RISER DIAGRAM TO INDICATE SIZE AND TYPE | | | OF PIPE AND WIRE FROM UTILITY TO MAIN SERVICE | | | DISCONNECT TO DISTRIBUTION TO TRAILER. CONFIRM AMPACITY | | | OF CONDUCTORS ARE ADAQUATE TO SUPPORT TOTAL CONNECTED | | | LOAD COMPUTED IN LOAD CALCULATION. | | | 4) A PANEL SCHEDULE TO INDICATE OCP AND CIRCUITS | | | INVOLVED. | | | | | | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, | | | 561-805-6717 OR [email protected] |
|