2014-06-11 08:54:352010 FBC
  
 DENIED BY MECHANICAL
  
 THE MECHANICAL PLANS SHOW NEW DUCT WORK AND THE SCOPE
 OF WORK SPECIFIES THE EXISTING A/C UNIT IS TO BE
 REPLACED AND RELOCATED.
  
 1) SUBMIT TWO SETS OF EQUIPMENT SIZING CALCULATIONS AND
 AHRI CERTIFICATIONS FOR THE NEW A/C EQUIPMENT. FBCR
 M1401.3
  
 2) SPECIFY THE CFMS AT EACH SUPPLY OUTLET. CITY
 AMENDMENTS 107.3.5.3
  
 3) SPECIFY THE SIZE OF THE SUPPLY DUCT FROM THE A/H TO
 THE DISTRIBUTION BOX BY THE FIREPLACE AND THE SIZE OF
 THE SUPPLY DUCT TO THE PANTRY ON THE PLANS. CITY
 AMENDMENTS 107.3.5.3
  
 4) LABEL THE ROOM TYPES ON THE PLANS. (IE BEDROOM,
 MASTER SUITE, ETC.) CITY AMENDMENTS 107.2.1 & 107.3.5.3
  
 5) SPECIFY THE SIZE OF THE RETURN AIR DUCT. CITY
 AMENDMENTS 107.3.5.3
  
 6) SHOW COMPLIANCE WITH FBCR M1602.4 FOR BALANCED
 RETURN AIR.
  
 7) THE PLANS HAVE WHAT APPEARS TO BE A DISCONNECT IN
 THE ROOM IN FRONT OF THE FIREPLACE. PLEASE CLARIFY.
 CITY AMENDMENTS 107.2.1
  
 8) A DISCONNECT AND APPLIANCE SERVICE RECEPTACLE OUTLET
 WILL BE REQUIRED FOR THE RELOCATED CONDENSING UNIT. NEC
 440.11 & 210.63
  