| Plan Review Notes For Permit 14060384 |
| Permit Number |
14060384 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-06-11 08:54:35 | 2010 FBC | | | | | | DENIED BY MECHANICAL | | | | | | THE MECHANICAL PLANS SHOW NEW DUCT WORK AND THE SCOPE | | | OF WORK SPECIFIES THE EXISTING A/C UNIT IS TO BE | | | REPLACED AND RELOCATED. | | | | | | 1) SUBMIT TWO SETS OF EQUIPMENT SIZING CALCULATIONS AND | | | AHRI CERTIFICATIONS FOR THE NEW A/C EQUIPMENT. FBCR | | | M1401.3 | | | | | | 2) SPECIFY THE CFMS AT EACH SUPPLY OUTLET. CITY | | | AMENDMENTS 107.3.5.3 | | | | | | 3) SPECIFY THE SIZE OF THE SUPPLY DUCT FROM THE A/H TO | | | THE DISTRIBUTION BOX BY THE FIREPLACE AND THE SIZE OF | | | THE SUPPLY DUCT TO THE PANTRY ON THE PLANS. CITY | | | AMENDMENTS 107.3.5.3 | | | | | | 4) LABEL THE ROOM TYPES ON THE PLANS. (IE BEDROOM, | | | MASTER SUITE, ETC.) CITY AMENDMENTS 107.2.1 & 107.3.5.3 | | | | | | 5) SPECIFY THE SIZE OF THE RETURN AIR DUCT. CITY | | | AMENDMENTS 107.3.5.3 | | | | | | 6) SHOW COMPLIANCE WITH FBCR M1602.4 FOR BALANCED | | | RETURN AIR. | | | | | | 7) THE PLANS HAVE WHAT APPEARS TO BE A DISCONNECT IN | | | THE ROOM IN FRONT OF THE FIREPLACE. PLEASE CLARIFY. | | | CITY AMENDMENTS 107.2.1 | | | | | | 8) A DISCONNECT AND APPLIANCE SERVICE RECEPTACLE OUTLET | | | WILL BE REQUIRED FOR THE RELOCATED CONDENSING UNIT. NEC | | | 440.11 & 210.63 | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|