2014-06-14 14:06:20DATE: 6/14/2014
 PROJECT: 5015 N. FLAGLER DR.
 PERMIT#: 14060367
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 ELECTRICAL PLAN REVIEW
  
 1ST REVIEW
 ACTION: DENIED
  
 HOLD PLACED ON PERMIT. ELECTRICAL CONTRACROR REQUIRED
 FOR ELECTRICAL PERMIT. GAS CERTIFIED PLUMBER REQUIRED
 FOR GAS PERMIT APPLICATION IS SIGNED BY A GC WITH ONLY
 A CGC LICENSE IN THE SYSTEM.
 FIELD VERIFY PANELS ARE NOT LOCATED IN THE BATHROOMS.
 NEC 240.24.(E)
 VERIFY THE CLEARANCES ARE MAINTAINED PER NEC 110.26