Plan Review Notes
Plan Review Notes For Permit 14060362
Permit Number 14060362
Review Stop B
Sequence Number 1
Notes
Date Text
2014-06-30 11:02:43****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. REVISE FLOOR PLAN TO PROVIDE THE FOLLOWING
 INFORMATION FOR BEDROOMS #1 & #2; FBC R310, FBC EB
 604.1. THE CLEAR OPENING CANNOT BE REDUCED BY MORE THAN
 5%:
  
 REVISE PLAN TO STATE WHAT TYPE OF WINDOW IS THERE NOW
 IN BEDROOMS #1 & #2 - AWNING, CASEMENT, SINGLE HUNG?
  
 REVISE PLAN TO STATE WHAT THE EXISTING CLEAR OPENING
 DIMENSIONS ARE FOR BEDROOMS #1 & #2. CLEAR OPENING IS
 THE OPENING WHICH EXISTS WHEN THE WINDOW IS FULLY OPEN.
  
 REVISE PLAN TO STATE WHAT THE PROPOSED CLEAR OPENING
 DIMENSIONS ARE FOR THESE WINDOWS. THIS CAN BE OBTAINED
 FROM THE MANUFACTURER
  
  