| Plan Review Notes For Permit 14060352 |
| Permit Number |
14060352 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-06-12 08:27:31 | APPROVED AS NOTED: AS PER NEC THE INTERIOR OF AN | | | UNDERGROUND (OR IN CONCRETE SLAB) RACEWAY SHALL BE | | | CONSIDERED A WET LOCATION; ALL CONDUCTORS WITHIN THE | | | RACEWAY SHALL BE LISTED ACCORDINGLY. |
|