Plan Review Notes
Plan Review Notes For Permit 14060348
Permit Number 14060348
Review Stop B
Sequence Number 1
Notes
Date Text
2014-06-25 10:35:20BUILDING PLAN REVIEW
 PERMIT: 14060348
 ADD: 1301 BELVEDERE RD
 CONT: TBD
 TEL: (267)251-8336
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. JUNE 25/2014
 ACTION: DENIED
  
 1) SHEET A111 INDICATES CONTRACTOR IS TO PROVIDE
 ENGINEERED STRUCTURAL SOFFIT DRAWINGS, THESE DRAWINGS
 ARE TO BE REVIEWED BY THE DESIGNER OF RECORD BEFORE
 BEING SUBMITTED TO THE BUILDING DEPARTMENT. FL
 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC.
  
 2) SHEET A111 INDICATES A NEW CLEAR ACRYLIC PANEL ON
 STEEL CANOPY FRAMING, DETAIL # 19 ON A510 BOTH OF THESE
 DETAILS ARE MORE OF A
 RENDERING, THERE ARE NO STRUCTURAL COMPONENTS PROVIDED
 IN TYPE OF MATERIALS FOR THE FRAMING MEMBERS, SIZE,
 THICKNESS OF STRUCTURAL MEMBERS, WELDS OR HOW THE
 GLAZING WILL BE ATTACHED, THICKNESS OF GLAZING NOR
 SIZE. 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS. CONSTRUCTION
 DOCUMENTS SHALL BE OF SUFFICIENT CLARITY TO INDICATE
 THE LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED
 AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL.
  
 3) SHEET A501 DETAIL # 1 INDICATES A NEW ALUMINUM
 STOREFRONT SYSTEM, PLEASE PROVIDE COMPLIANCE WITH :
 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.41
 COMPONENTS & CLADDING
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(C) PANEL WALLS: STOREFRONTS,
  
 4) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 5) SHEET S001 THE WIND DESIGN CRITERIA INDICATES THE
 JOB SITE TO BE LOCATED IN A "B" EXPOSURE. PLEASE SEE
 THIS IS CONSIDERED A "C" SURFACE ROUGHNESS TO THE
 NORTHEAST AND SOUTHEAST. 2010 FBC-B 1609.4.2 THIS
 SURFACE ROUGHNESS SHALL ALSO APPLY TO ANY BUILDING
 LOCATED WITHIN SURFACE ROUGHNESS B-TYPE TERRAIN WHERE
 THE BUILDING IS WITHIN 100 FEET HORIZONTALLY IN ANY
 DIRECTION OF OPEN AREAS OF SURFACE ROUGHNESS C OR
 D-TYPE TERRAIN THAT EXTENDS MORE THAN 600 FEET (182.9
 M) AND WIDTH GREATER THAN 150 FEET IN THE UPWIND
 DIRECTION. THE PRESSURES ON THIS BUILDING WILL CHANGE
 DRAMATICALY SINCE TABLE 1609.7(2) SHOWS THE MULTIPLIERS
 REQUIED FOR A "C" EXPOSURE. POSITIVE PRESSURES BUILD UP
 FROM THE BOTTOM, NEGATIVE PRESSURES ARE TAKEN FROM THE
 ROOF LEVEL. PLEASE ALSO SHOW IN YOUR TABLE THE
 TRIBUTARY AREA FOR THE PRESSURES PROVIDED.
  
 6) SHEET A510 DETAIL # 5 INDICATES THE USE OF STEEL
 FRAMING MEMBERS WITH SHEATHING, NEITHER THE
 ARCHITECTURAL NOR STRUCTURAL SHEETS PROVIDE THE TYPE OF
 SHEATHING TO BE INSTALLED, THICKNESS OF THE SHEATHING
 NOR THE TYPE OF FASTENERS THAT WILL BE USED IN THE
 INSTALATION OF THE SHEATHING.
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION, 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE
 OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE
 AND EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT
 IT WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 7) SHEET A510 DETAIL # 3 INDICATES THE INSTALATION OF
 ARRIS EXTERIOR THIN CLAD STONE, TO BE INSTALLED PER THE
 MANUFACTURERS RECOMENDATIONS. PLEASE PROVIDE DETAILS
 HOW THIS SYSTEM IS TO BE INSTALLED. 2010 FBC-B 1405.10
 ADHERED MASONRY VENEER. ADHERED MASONRY VENEER SHALL
 COMPLY WITH THE APPLICABLE REQUIREMENTS OF SECTION
 1405.10.1 AND SECTIONS 6.1 AND 6.3 OF TMS 402/ACI
 530/ASCE 5.
  
 8) SHEET A510 DETAIL # 5 INDICATES THE USE OF FLUID
 APPLIED FLEXIBLE ACRYLIC ROOFING, & SHEET A515 DETAIL #
 14 INDICATES THE USE OF TPO ROOFING PRODUCTS. PLEASE
 PROVIDE ROOFING PRODUCT APPROVALS FOR EACH OF THESE
 SYSTEMS. NOTE IF ZONES 2 & 3 WILL REQUIRE ENHANCED
 FASTENING AND IF A MIAMI-DADE NOA LIMITATION 7 OR 9 IS
 INDICATED FOR THE SUBSYSTEM. FLORIDA DEPARTMENT OF
 COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31)
 SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT
 WILL REQUIRE PRODUCT APPROVALS:
 (31)(D) ROOFING PRODUCTS AND ASSEMBLIES.
  
 9) SHEET A110 INDICATES WORK ON THE CURB. PLEASE
 PROVIDE COMPLIANCE WITH 2010 FLORIDA ACCESSIBILITY
 CODE, 503.1 GENERAL.
 PASSENGER LOADING ZONES SHALL COMPLY WITH 503.
  
 503.2 VEHICLE PULL-UP SPACE.
 PASSENGER LOADING ZONES SHALL PROVIDE A VEHICULAR
 PULL-UP SPACE 96 INCHES (2440 MM) WIDE MINIMUM AND 20
 FEET (6100 MM) LONG MINIMUM.
  
 503.3 ACCESS AISLE.
 PASSENGER LOADING ZONES SHALL PROVIDE ACCESS AISLES
 COMPLYING WITH 503 ADJACENT TO THE VEHICLE PULL-UP
 SPACE. ACCESS AISLES SHALL ADJOIN AN ACCESSIBLE ROUTE
 AND SHALL NOT OVERLAP THE VEHICULAR WAY.
  
 FIGURE 503.3
 PASSENGER LOADING ZONE ACCESS AISLE
  
 503.3.1 WIDTH.
 ACCESS AISLES SERVING VEHICLE PULL-UP SPACES SHALL BE
 60 INCHES (1525 MM) WIDE MINIMUM.
  
 503.3.2 LENGTH.
 ACCESS AISLES SHALL EXTEND THE FULL LENGTH OF THE
 VEHICLE PULL-UP SPACES THEY SERVE.
  
 503.3.3 MARKING.
 ACCESS AISLES SHALL BE MARKED SO AS TO DISCOURAGE
 PARKING IN THEM.
  
 503.4 FLOOR AND GROUND SURFACES.
 VEHICLE PULL-UP SPACES AND ACCESS AISLES SERVING THEM
 SHALL COMPLY WITH 302. ACCESS AISLES SHALL BE AT THE
 SAME LEVEL AS THE VEHICLE PULL-UP SPACE THEY SERVE.
 CHANGES IN LEVEL ARE NOT PERMITTED.
  
 10) SHEET A110 CANOPY, 502.5 VERTICAL CLEARANCE.
 PARKING SPACES FOR VANS AND ACCESS AISLES AND VEHICULAR
 ROUTES SERVING THEM SHALL PROVIDE A VERTICAL CLEARANCE
 OF 98 INCHES (2490 MM) MINIMUM.
  
 11) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER