2014-06-10 08:43:472010 FBC
  
 DENIED BY BUILDING
  
 1) THE ENGINEERING INDICATES THAT THIS HIGH RISE
 STRUCTURE HAS A 4 : 12 ROOF SLOPE. IN THE AERIAL
 PHOTOGRAPHS ON THE PROPERTY APPRAISER'S WEB SITE IT
 APPEARS THAT THIS BUILDING HAS A 0 SLOPE ROOF. PLEASE
 VERIFY. CITY AMENDMENTS 107.2.1
  
 2) ALL OF THE OPENINGS ARE SPECIFIED AS ZONE 4 ON THE
 ENGINEERING. THE DRAWING THAT WAS SUBMITTED APPEARS TO
 SHOW THAT AT LEAST PART OF SOME OF THE OPENINGS ARE
 LOCATED IN WALL ZONE 5. PLEASE PROVIDE A DIAGRAM OF THE
 BUILDING AND INDICATE THE LOCATION OF THIS UNIT.
  
 3) NOA NO. 12-0410.19 FOR THE SERIES ML-100 ALUMINUM
 TUB MULLIONS HAS BEEN SUPERSEDED. PLEASE SUBMIT THE
 CURRENT PRODUCT APPROVAL. DCA RULE 9N-3
  
 4) PLEASE CLARIFY THE COMPONENT THAT IS LOCATED AT EACH
 OPENING ON THE PLANS. FOR EXAMPLE OPENING NUMBERS 2, 3
 AND 4 APPEAR TO BE (4) PANEL SLIDING GLASS DOORS AND
 OPENING NUMBER 1 APPEARS TO BE A (3) PANEL SLIDING
 GLASS DOOR AS CIRCLED ON THE PRODUCT APPROVAL. HOWEVER,
 I DO NOT KNOW WHAT COMPONENTS WILL BE IN OPENINGS 5 AND
 6. CITY AMENDMENTS 107.2.1
  
 5) PLEASE INDICATE WHERE THE TUBE MULLION IS TO BE
 INSTALLED. INDICATE THE MULL SPAN AND OPENING SIZES ON
 EACH SIDE ON THE MULLION. CITY AMENDMENTS 107.2.1
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]