2014-06-16 11:23:57DATE: 6/16/2014
 PROJECT: ADAM - SUN ROOM
 PERMIT#: 14060303
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 1ST ELECTRICAL PLAN REVIEW
 ACTION: PROVISO.
  
 1) ALL 120V SINGE PHASE 15 AND 20AMP BRANCH CIRCUITS
 SUPPLYING OUTLETS INSTALLED IN DWELLING UNIT FAMILY
 ROOMS, DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES,
 DENS, BEDROOMS, SUNROOMS, RECREATION ROOMS, CLOSETS,
 HALLWAYS OR SIMILAR ROOMS OR AREAS SHALL BE PROTECTED
 BY A LISTED ARC-FAULT CIRCUIT INTERRUPTER
 COMBINATION-TYPE, INSTALLED TO PROVIDE PROTECTION OF
 THE BRANCH CIRCUIT. NEC 210.12(B) SEE ALSO 406.11
  
 2) FOR DWELLING UNITS, ATTACHED GARAGES, AND DETACHED
 GARAGES, WITH ELECTRIC POWER AT LEAST AT LEAST ONE WALL
 SWITCH CONTROLLED LIGHTING OUTLET SHALL BE INSTALLED TO
 PROVIDE ILLUMINATION ON THE EXTERIOR SIDE OF OUTDOOR
 ENTRANCES OR EXITS WITH GRADE LEVEL ACCESS. NEC
 210.70(2)(B)
  
 3) FOR A ONE-FAMILY DWELLING AND EACH UNIT OF A
 TWO-FAMILY DWELLING THAT IS AT GRADE LEVEL, AT LEAST
 ONE RECEPTACLE OUTLET ACCESSIBLE WHILE STANDING AT
 GRADE LEVEL AND LOCATED NOT MORE THAN 61/2FT ABOVE
 GRADE SHALL BE INSTALLED AT THE FRONT AND THE BACK OF
 THE DWELLING. UNLESS THERE IS ALREADY AN EXISTING
 RECEPTACLE OUTLET AT THE REAR OF THE DWELLING. NEC
 210.52(E)(1) SEE ALSO 210.8(A)(3), 406.8(B), 406.11
  
 4) ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF
 THE PERSON RESPONSIBLE FOR THE DESIGN. FBC 107.2.1
  